3-8
C70 Capacitor Bank Protection and Control System
GE Multilin
3.1 DESCRIPTION
3 HARDWARE
3
3.1.3 REAR TERMINAL LAYOUT
Figure 3–10: REAR TERMINAL VIEW
Do not touch any rear terminals while the relay is energized!
The relay follows a convention with respect to terminal number assignments which are three characters long assigned in
order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the
first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following
figure for an example of rear terminal assignments.
Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS
834752A2.CDR
X
W
V
U
T
S
P
N
M
L
K
J
H
D
G
F
B
R
8
4
7
3
6
2
5
1
b
8
4
7
3
6
2
5
1
a
a
b
c
a
b
c
4
3
2
1
b
4
3
2
1
a
IN
OUT
Tx1
Tx2
Rx2
Rx1
CH1
Tx
CH2
Rx
CH1
CH2
®
®
Technical Support:
Tel: (905) 294-6222
Fax: (905) 201-2098
Model:
Mods:
Wiring Diagram:
Inst. Manual:
Serial Number:
Firmware:
Mfg. Date:
C70D00HCHF8AH6AL6BN8BU6AX7A
000
ZZZZZZ
D
MAZB98000029
D
2005/01/05
Control Power:
Contact Inputs:
Contact Outputs:
88-300V DC @ 35W / 77-265V AC @ 35VA
300V DC Max 10mA
Standard Pilot Duty / 250V AC 7.5A
360V A Resistive / 125V DC Break
4A @ L/R = 40mS / 300W
RATINGS:
C70
Made in
Canada
- M A A B 9 7 0 0 0 0 9 9 -
Capacitor Bank Protection Relay
http://www.GEIndustrial.com/Multilin
GE Multilin
Optional
Ethernet
switch
Optional
direct
input/output
module
CPU module
(Ethernet not
available when
ordered with
Ethernet switch)
Optional
contact
input/output
module
CT/VT
module
Power
supply
module
Tx1
Tx2
Rx1
Rx2
Tx1
Tx2
a
b
c
Optional
contact
input/output
module
WARNING
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...