GE Multilin
C70 Capacitor Bank Protection and Control System
D-7
APPENDIX D
D.1 OVERVIEW
D
Spontaneous Transmission:
4
Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of an information
object. The particular information object addresses for which double transmission is enabled are defined in a project-
specific list.
Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1
Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1
Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1
Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1
Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1
Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
Clock synchronization:
4
Clock synchronization (optional, see Clause 7.6)
Command transmission:
4
Direct command transmission
Direct setpoint command transmission
4
Select and execute command
Select and execute setpoint command
4
C_SE ACTTERM used
4
No additional definition
4
Short pulse duration (duration determined by a system parameter in the outstation)
4
Long pulse duration (duration determined by a system parameter in the outstation)
4
Persistent output
4
Supervision of maximum delay in command direction of commands and setpoint commands
Maximum allowable delay of commands and setpoint commands:
10 s
Transmission of integrated totals:
4
Mode A: Local freeze with spontaneous transmission
4
Mode B: Local freeze with counter interrogation
4
Mode C: Freeze and transmit by counter-interrogation commands
4
Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously
4
Counter read
4
Counter freeze without reset
4
Global
4
Group 1
4
Group 5
4
Group 9
4
Group 13
4
Group 2
4
Group 6
4
Group 10
4
Group 14
4
Group 3
4
Group 7
4
Group 11
4
Group 15
4
Group 4
4
Group 8
4
Group 12
4
Group 16
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...