5-86
C70 Capacitor Bank Protection and Control System
GE Multilin
5.5 FLEXLOGIC™
5 SETTINGS
5
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–8: C70 FLEXLOGIC™ OPERANDS (Sheet 1 of 8)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
CONTROL
PUSHBUTTONS
CONTROL PUSHBTN 1 ON
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
DIRECT DEVICES
DIRECT DEVICE 1On
↓
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
↓
DIRECT DEVICE 16Off
Flag is set, logic=1
↓
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
DIRECT INPUT/
OUTPUT
CHANNEL
MONITORING
DIR IO CH1 CRC ALARM
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level.
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level.
The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only).
The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only).
ELEMENT:
Auxiliary
overvoltage
AUX OV1 PKP
AUX OV1 DPO
AUX OV1 OP
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
AUX OV2 to AUX OV3
Same set of operands as shown for AUX OV1
ELEMENT:
Automatic voltage
regulator
AVR 1 CLOSE PKP
AVR 1 CLOSE OP
AVR 1 CLOSE DPO
AVR 1 OPEN PKP
AVR 1 OPEN OP
AVR 1 OPEN DPO
Automatic voltage regulator 1 picked up; close command pending
Automatic voltage regulator 1 issued a close command
Close command of automatic voltage regulator 1 dropped out
Automatic voltage regulator 1 picked up; open command pending
Automatic voltage regulator 1 issued an open command
Open command of automatic voltage regulator 1 dropped out
AVR 2 to AVR 3
Same set of operands as shown for AVR 1
ELEMENT:
Bank phase
overvoltage
BANK OV 1 STG 1A PKP
BANK OV 1 STG 1B PKP
BANK OV 1 STG 1C PKP
BANK OV 1 STG 2A PKP
BANK OV 1 STG 2B PKP
BANK OV 1 STG 2C PKP
BANK OV 1 STG 3A PKP
BANK OV 1 STG 3B PKP
BANK OV 1 STG 3C PKP
BANK OV 1 STG 4A PKP
BANK OV 1 STG 4B PKP
BANK OV 1 STG 4C PKP
BANK OV 1 PKP A
BANK OV 1 PKP B
BANK OV 1 PKP C
BANK OV 1 PKP
BANK OV 1 DPO
BANK OV 1 STG 1A OP
BANK OV 1 STG 1B OP
BANK OV 1 STG 1C OP
BANK OV 1 STG 2A OP
BANK OV 1 STG 2B OP
BANK OV 1 STG 2C OP
BANK OV 1 STG 3A OP
BANK OV 1 STG 3B OP
BANK OV 1 STG 3C OP
BANK OV 1 STG 4A OP
BANK OV 1 STG 4B OP
BANK OV 1 STG 4C OP
BANK OV 1 OP A
BANK OV 1 OP B
BANK OV 1 OP C
BANK OV 1 OP
Bank overvoltage element 1 picked up in phase A of stage 1
Bank overvoltage element 1 picked up in phase B of stage 1
Bank overvoltage element 1 picked up in phase C of stage 1
Bank overvoltage element 1 picked up in phase A of stage 2
Bank overvoltage element 1 picked up in phase B of stage 2
Bank overvoltage element 1 picked up in phase C of stage 2
Bank overvoltage element 1 picked up in phase A of stage 3
Bank overvoltage element 1 picked up in phase B of stage 3
Bank overvoltage element 1 picked up in phase C of stage 3
Bank overvoltage element 1 picked up in phase A of stage 4
Bank overvoltage element 1 picked up in phase B of stage 4
Bank overvoltage element 1 picked up in phase C of stage 4
Bank overvoltage element 1 picked up in phase A
Bank overvoltage element 1 picked up in phase B
Bank overvoltage element 1 picked up in phase C
Bank overvoltage element 1 picked up
Bank overvoltage element 1 dropped out
Bank overvoltage element 1 operated in phase A of stage 1
Bank overvoltage element 1 operated in phase B of stage 1
Bank overvoltage element 1 operated in phase C of stage 1
Bank overvoltage element 1 operated in phase A of stage 2
Bank overvoltage element 1 operated in phase B of stage 2
Bank overvoltage element 1 operated in phase C of stage 2
Bank overvoltage element 1 operated in phase A of stage 3
Bank overvoltage element 1 operated in phase B of stage 3
Bank overvoltage element 1 operated in phase C of stage 3
Bank overvoltage element 1 operated in phase A of stage 4
Bank overvoltage element 1 operated in phase B of stage 4
Bank overvoltage element 1 operated in phase C of stage 4
Bank overvoltage element 1 operated in phase A
Bank overvoltage element 1 operated in phase B
Bank overvoltage element 1 operated in phase C
Bank overvoltage element 1 operated
BANK OV 2 to BANK OV 3
Same set of operands as shown for BANK OV 1