GE Multilin
C70 Capacitor Bank Protection and Control System
5-91
5 SETTINGS
5.5 FLEXLOGIC™
5
ELEMENT:
Disconnect switch
SWITCH 1 OFF CMD
SWITCH 1 ON CMD
SWITCH 1
Φ
A BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
A CLSD
SWITCH 1
Φ
A OPEN
SWITCH 1
Φ
B BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
B CLSD
SWITCH 1
Φ
B OPEN
SWITCH 1
Φ
C BAD ST
SWITCH 1
Φ
A INTERM
SWITCH 1
Φ
C CLSD
SWITCH 1
Φ
C OPEN
SWITCH 1 BAD STATUS
SWITCH 1 CLOSED
SWITCH 1 OPEN
SWITCH 1 DISCREP
SWITCH 1 TROUBLE
Disconnect switch 1 open command initiated
Disconnect switch 1 close command initiated
Disconnect switch 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase A is closed
Disconnect switch 1 phase A is open
Disconnect switch 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase B is closed
Disconnect switch 1 phase B is open
Disconnect switch 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
Disconnect switch 1 phase C is closed
Disconnect switch 1 phase C is open
Disconnect switch 1 bad status is detected on any pole
Disconnect switch 1 is closed
Disconnect switch 1 is open
Disconnect switch 1 has discrepancy
Disconnect switch 1 trouble alarm
SWITCH 2...
Same set of operands as shown for SWITCH 1
ELEMENT:
Time of day timer
TIME OF DAY 1 ON
TIME OF DAY 1 START
TIME OF DAY 1 STOP
Time of day timer 1 is on
One-second pulse at set time of day timer 1 start time
One-second pulse at set time of day timer 1 stop time
TIME OF DAY 2 to 5
Same set of operands as shown for TIME OF DAY 1
ELEMENT
Trip bus
TRIP BUS 1 PKP
TRIP BUS 1 OP
Asserted when the trip bus 1 element picks up.
Asserted when the trip bus 1 element operates.
TRIP BUS 2...
Same set of operands as shown for TRIP BUS 1
ELEMENT:
Voltage differential
VOLT DIF 1 STG1A PKP
VOLT DIF 1 STG1B PKP
VOLT DIF 1 STG1C PKP
VOLT DIF 1 STG2A PKP
VOLT DIF 1 STG2B PKP
VOLT DIF 1 STG2C PKP
VOLT DIF 1 STG3A PKP
VOLT DIF 1 STG3B PKP
VOLT DIF 1 STG3C PKP
VOLT DIF 1 STG4A PKP
VOLT DIF 1 STG4B PKP
VOLT DIF 1 STG4C PKP
VOLT DIF 1 PKP A
VOLT DIF 1 PKP B
VOLT DIF 1 PKP C
VOLT DIF 1 PKP
VOLT DIF 1 DPO
VOLT DIF 1 STG1A OP
VOLT DIF 1 STG1B OP
VOLT DIF 1 STG1C OP
VOLT DIF 1 STG2A OP
VOLT DIF 1 STG2B OP
VOLT DIF 1 STG2C OP
VOLT DIF 1 STG3A OP
VOLT DIF 1 STG3B OP
VOLT DIF 1 STG3C OP
VOLT DIF 1 STG4A OP
VOLT DIF 1 STG4B OP
VOLT DIF 1 STG4C OP
VOLT DIF 1 OP A
VOLT DIF 1 OP B
VOLT DIF 1 OP C
VOLT DIF 1 OP
Voltage differential element 1 picked up in phase A of stage 1
Voltage differential element 1 picked up in phase B of stage 1
Voltage differential element 1 picked up in phase C of stage 1
Voltage differential element 1 picked up in phase A of stage 2
Voltage differential element 1 picked up in phase B of stage 2
Voltage differential element 1 picked up in phase C of stage 2
Voltage differential element 1 picked up in phase A of stage 3
Voltage differential element 1 picked up in phase B of stage 3
Voltage differential element 1 picked up in phase C of stage 3
Voltage differential element 1 picked up in phase A of stage 4
Voltage differential element 1 picked up in phase B of stage 4
Voltage differential element 1 picked up in phase C of stage 4
Voltage differential element 1 picked up in phase A
Voltage differential element 1 picked up in phase B
Voltage differential element 1 picked up in phase C
Voltage differential element 1 picked up
Voltage differential element 1 dropped out
Voltage differential element 1 operated in phase A of stage 1
Voltage differential element 1 operated in phase B of stage 1
Voltage differential element 1 operated in phase C of stage 1
Voltage differential element 1 operated in phase A of stage 2
Voltage differential element 1 operated in phase B of stage 2
Voltage differential element 1 operated in phase C of stage 2
Voltage differential element 1 operated in phase A of stage 3
Voltage differential element 1 operated in phase B of stage 3
Voltage differential element 1 operated in phase C of stage 3
Voltage differential element 1 operated in phase A of stage 4
Voltage differential element 1 operated in phase B of stage 4
Voltage differential element 1 operated in phase C of stage 4
Voltage differential element 1 operated in phase A
Voltage differential element 1 operated in phase B
Voltage differential element 1 operated in phase C
Voltage differential element 1 operated
VOLT DIF 2 to 3
Same set of operands as shown for VOLT DIF 1 above
FIXED OPERANDS
Off
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On
Logic = 1. Can be used as a test setting.
Table 5–8: C70 FLEXLOGIC™ OPERANDS (Sheet 6 of 8)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION