GE Multilin
C70 Capacitor Bank Protection and Control System
7-1
7 COMMANDS AND TARGETS
7.1 COMMANDS
7
7 COMMANDS AND TARGETS 7.1COMMANDS
7.1.1 COMMANDS MENU
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the
Security
section of chapter 5 for details. The following flash mes-
sage appears after successfully command entry:
7.1.2 CAPACITOR BANK AUTOMATIC SETTINGS
a) MAIN MENU
PATH: COMMANDS
Ö
CAPACITOR BANK AUTO SETTING
The relay provides for automatic calculations of proper balancing (matching) factors of the sensitive capacitor bank protec-
tion functions. The following screens display the suggested values of the balancing factors, and prompt the user to apply
them if desired so. If applied from this command level, a given value is placed into the setting file and applied instanta-
neously in all setting groups of the relay with the same source as the active group during the auto-setting procedure.
COMMANDS
Ø
MESSAGE
CAPACITOR BANK
AUTO SETTING
MESSAGE
COMMANDS
VIRTUAL INPUTS
MESSAGE
COMMANDS
CLEAR RECORDS
MESSAGE
COMMANDS
SET DATE AND TIME
MESSAGE
COMMANDS
RELAY MAINTENANCE
COMMAND
EXECUTED
CAPACITOR BANK
AUTO SETTING
VOLTAGE
DIFFERENTIAL
MESSAGE
NEUTRAL VOLTAGE
UNBALANCE
MESSAGE
PHASE CURRENT
UNBALANCE
MESSAGE
NEUTRAL CURRENT
UNBALANCE