GE Multilin
C70 Capacitor Bank Protection and Control System
B-23
APPENDIX B
B.4 MEMORY MAPPING
B
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency And Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Breaker control (read/write settings)
4700
Breaker 1 function
0 to 1
---
1
F102
0 (Disabled)
4701
Breaker 1 name
---
---
---
F206
“Bkr 1"
4704
Breaker 1 mode
0 to 1
---
1
F157
0 (3-Pole)
4705
Breaker 1 open
0 to 65535
---
1
F300
0
4706
Breaker 1 close
0 to 65535
---
1
F300
0
4707
Breaker 1 phase A / three-pole closed
0 to 65535
---
1
F300
0
4708
Breaker 1 phase B closed
0 to 65535
---
1
F300
0
4709
Breaker 1 phase C closed
0 to 65535
---
1
F300
0
470A
Breaker 1 external alarm
0 to 65535
---
1
F300
0
470B
Breaker 1 alarm delay
0 to 1000000
s
0.001
F003
0
470D
Breaker 1 pushbutton control
0 to 1
---
1
F102
0 (Disabled)
470E
Breaker 1 manual close recall time
0 to 1000000
s
0.001
F003
0
4710
Breaker 1 out of service
0 to 65535
---
1
F300
0
4711
Breaker 1 block open
0 to 65535
---
1
F300
0
4712
Breaker 1 block close
0 to 65535
---
1
F300
0
4713
Breaker 1 phase A / three-pole opened
0 to 65535
---
1
F300
0
4714
Breaker 1 phase B opened
0 to 65535
---
1
F300
0
4715
Breaker 1 phase C opened
0 to 65535
---
1
F300
0
4716
Breaker 1 operate time
0 to 2
s
0.001
F001
70
4717
Breaker 1 events
0 to 1
---
1
F102
0 (Disabled)
4718
Reserved
---
---
---
---
---
4719
...Repeated for breaker 2
4732
...Repeated for breaker 3
474B
...Repeated for breaker 4
4764
...Repeated for breaker 5
477D
...Repeated for breaker 6
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
48F0
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
““
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
Table B–9: MODBUS MEMORY MAP (Sheet 16 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...