B-30
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
6576
Time of day timer 1 events
0 to 1
---
1
F102
0 (Disabled)
6577
...Repeated for time of day timer 2
657E
...Repeated for time of day timer 3
6585
...Repeated for time of day timer 4
658C
...Repeated for time of day timer 5
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 65535
---
1
F300
0
7007
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7008
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7009
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to Ground)
700A
Reserved (6 items)
0 to 1
---
1
F001
0
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 65535
---
1
F300
0
7046
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7047
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7048
Reserved (8 items)
0 to 1
---
1
F001
0
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280
Neutral Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7281
Neutral Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7282
Neutral Directional Overcurrent 1 Polarizing
0 to 2
---
1
F230
0 (Voltage)
7283
Neutral Directional Overcurrent 1 Forward ECA
-90 to 90
° Lag
1
F002
75
7284
Neutral Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7285
Neutral Directional Overcurrent 1 Forward Pickup
0.002 to 30
pu
0.001
F001
50
7286
Neutral Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7287
Neutral Directional Overcurrent 1 Reverse Pickup
0.002 to 30
pu
0.001
F001
50
7288
Neutral Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7289
Neutral Directional Overcurrent 1 Block
0 to 65535
---
1
F300
0
728A
Neutral Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
728B
Neutral Directional Overcurrent 1 Polarizing Voltage
0 to 1
---
1
F231
0 (Calculated V0)
728C
Neutral Directional Overcurrent 1 Op Current
0 to 1
---
1
F196
0 (Calculated 3I0)
728D
Neutral Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
728E
Neutral Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
728F
Reserved
0 to 1
---
1
F001
0
dcmA Inputs (Read/Write Setting) (24 modules)
7300
dcmA Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
7301
dcmA Inputs 1 ID
---
---
---
F205
“DCMA I 1"
7307
Reserved 1 (4 items)
0 to 65535
---
1
F001
0
730B
dcmA Inputs 1 Units
---
---
---
F206
“mA”
730E
dcmA Inputs 1 Range
0 to 6
---
1
F173
6 (4 to 20 mA)
730F
dcmA Inputs 1 Minimum Value
-9999.999 to 9999.999
---
0.001
F004
4000
7311
dcmA Inputs 1 Maximum Value
-9999.999 to 9999.999
---
0.001
F004
20000
7313
Reserved (5 items)
0 to 65535
---
1
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT