5-138
L90 Line Current Differential System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
LED INDICATORS:
Fixed front panel
LEDs
LED IN SERVICE
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
Asserted when the front panel IN SERVICE LED is on.
Asserted when the front panel TROUBLE LED is on.
Asserted when the front panel TEST MODE LED is on.
Asserted when the front panel TRIP LED is on.
Asserted when the front panel ALARM LED is on.
Asserted when the front panel PICKUP LED is on.
Asserted when the front panel VOLTAGE LED is on.
Asserted when the front panel CURRENT LED is on.
Asserted when the front panel FREQUENCY LED is on.
Asserted when the front panel OTHER LED is on.
Asserted when the front panel PHASE A LED is on.
Asserted when the front panel PHASE B LED is on.
Asserted when the front panel PHASE C LED is on.
Asserted when the front panel NEUTRAL/GROUND LED is on.
LED INDICATORS:
LED test
LED TEST IN PROGRESS
An LED test has been initiated and has not finished.
LED INDICATORS:
User-programmable
LEDs
LED USER 1
Asserted when user-programmable LED 1 is on.
LED USER 2 to 48
The operand above is available for user-programmable LEDs 2 through 48.
PASSWORD
SECURITY
ACCESS LOC SETG OFF
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
Asserted when local setting access is disabled.
Asserted when local setting access is enabled.
Asserted when local command access is disabled.
Asserted when local command access is enabled.
Asserted when remote setting access is disabled.
Asserted when remote setting access is enabled.
Asserted when remote command access is disabled.
Asserted when remote command access is enabled.
Asserted when a password entry fails while accessing a password protected
level of the L90.
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 2 On
REMOTE DEVICE 2 On
REMOTE DEVICE 16 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
REMOTE DEVICE 1 Off
REMOTE DEVICE 2 Off
REMOTE DEVICE 3 Off
REMOTE DEVICE 16 Off
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
Reset command is operated (set by all three operands below).
Communications source of the reset command.
Operand (assigned in the
INPUTS/OUTPUTS
RESETTING
menu) source
of the reset command.
Reset key (pushbutton) source of the reset command.
SELF-
DIAGNOSTICS
(See
Relay Self-
tests
descriptions in
Chapter 7:
Commands and
Targets)
ANY MAJOR ERROR
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
CLOCK UNSYNCHRONIZED
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
FLEXLOGIC ERR TOKEN
LATCHING OUT ERROR
MAINTENANCE ALERT
FIRST ETHERNET FAIL
PROCESS BUS FAILURE
PTP FAILURE
REMOTE DEVICE OFF
RRTD COMM FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
The battery is not functioning. Return power supply module to manufacturer.
Relay is not synchronized to the international time standard
A direct device is configured but not connected
The Direct I/O settings is for a connection that is not in a ring
The configuration of modules does not match the stored order code
A FlexLogic equation is incorrect
A difference is detected between the desired and actual latch contact state
A subset of the minor self-test errors generated, see Chapter 7
Link failure detected. See description in
Chapter 7: Commands and targets.
See description in
Chapter 7: Commands and targets
"Bad PTP Signal" self-test as described in Chapter 7
One or more GOOSE devices are not responding
See description in
Chapter 7: Commands and targets
See description in
Chapter 7: Commands and targets
See description in
Chapter 7: Commands and targets
SNTP server is not responding
See description in
Chapter 7: Commands and targets
Monitors ambient temperature and maximum operating temperature
The product setup>installation>relay settings setting is not programmed
TEMPERATURE
MONITOR
TEMP MONITOR
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
Table 5–12: L90 FLEXLOGIC OPERANDS (Sheet 10 of 11)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...