GE Multilin
L90 Line Current Differential System
B-27
APPENDIX B
B.4 MEMORY MAPPING
B
3F06
Field Unit RTD 1 Origin
0 to 1
---
1
F205
"RTD 1"
3F07
Field Unit RTD 1 Type
0 to 2
---
1
F259
0 (100 Ohm
Nickel)
3F08
...Repeated for Field Unit RTD 2
3F10
...Repeated for Field Unit RTD 3
3F18
...Repeated for Field Unit RTD 4
3F20
...Repeated for Field Unit RTD 5
3F28
...Repeated for Field Unit RTD 6
3F30
...Repeated for Field Unit RTD 7
3F38
...Repeated for Field Unit RTD 8
Field Unit Transducers (Read/Write Setting) (8 modules)
3F40
Field Unit Transducer 1 Name
0 to 1
---
1
F205
"TRD 1"
3F46
Field Unit Transducer 1 Origin
0 to 24
---
1
F53
0 (none)
3F47
Field Unit Transducer 1 Range
0 to 9
---
1
F246
6 (0...20mA)
3F48
Field Unit Transducer 1 Min Value
-9999.999 to 9999.999
---
0.01
F004
0
3F4A
Field Unit Transducer 1 Max Value
-9999.999 to 9999.999
---
0.001
F004
100000
3F4C
Field Unit Transducer 1 Units
---
---
---
F206
(none)
3F4F
...Repeated for Field Unit Transducer 2
3F5E
...Repeated for Field Unit Transducer 3
3F6D
...Repeated for Field Unit Transducer 4
3F7C
...Repeated for Field Unit Transducer 5
3F8B
...Repeated for Field Unit Transducer 6
3F9A
...Repeated for Field Unit Transducer 7
3FA9
...Repeated for Field Unit Transducer 8
Field Unit Identifiers (Read Only) (8 modules)
3FB8
Attached Field Unit 1 Serial Number
---
---
1
F205
(none)
3FBE
Attached Filed Unit 1 Port Number
---
---
1
F001
0
3FBF
Attached Field Unit 1 Type
0 to 3
---
1
F243
0 (CC-05)
3FC0
Field Unit 1 Status
0 to 4
---
1
F262
0 (Disabled)
3FC1
...Repeated for Field Unit 2
3FCA
...Repeated for Field Unit 3
3FD3
...Repeated for Field Unit 4
3FDC
...Repeated for Field Unit 5
3FE5
...Repeated for Field Unit 6
3FEE
...Repeated for Field Unit 7
3FF7
...Repeated for Field Unit 8
Passwords (Read/Write Command)
4000
Command Password Setting
0 to 4294967295
---
1
F202
0
Passwords (Read/Write Setting)
400A
Setting Password Setting
0 to 4294967295
---
1
F202
0
Passwords (Read/Write)
4014
Command Password Entry
0 to 4294967295
---
1
F202
(none)
401E
Setting Password Entry
0 to 4294967295
---
1
F202
(none)
Passwords (Read Only)
4028
Command Password Status
0 to 1
---
1
F102
0 (Disabled)
4029
Setting Password Status
0 to 1
---
1
F102
0 (Disabled)
Passwords (Read/Write Setting)
402A
Command Password Access Timeout
5 to 480
min
1
F001
5
402B
Setting Password Access Timeout
5 to 480
min
1
F001
30
402C
Invalid Password Attempts
2 to 5
---
1
F001
3
402D
Password Lockout Duration
5 to 60
min
1
F001
5
Passwords (Read/Write)
402E
Password Access Events
0 to 1
---
1
F102
0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 19 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...