B-32
L90 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
438E
...Repeated for Route 6
Installation (Read/Write Setting)
43E0
Relay Programmed State
0 to 1
---
1
F133
0 (Not
Programmed)
43E1
Relay Name
---
---
---
F202
“Relay-1”
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
0 to 1
---
1
F102
1 (Enabled)
4442
User Programmable Direct Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4443
User Programmable Remote Device Off Function
0 to 1
---
1
F102
1 (Enabled)
4444
User Programmable First Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4445
User Programmable Secondary Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
444A
Process Bus Failure Operand
0 to 4294967295
---
1
F300
0
444C
PTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
444D
User Programmable Third Ethernet Fail Function
0 to 1
---
1
F102
0 (Disabled)
444E
User Programmable SFP Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
4484
...Repeated for CT Bank 2
4488
...Repeated for CT Bank 3
448C
...Repeated for CT Bank 4
4490
...Repeated for CT Bank 5
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
4501
Phase VT 1 Secondary
25 to 240
V
0.1
F001
664
4502
Phase VT 1 Ratio
1 to 24000
:1
1
F060
1
4504
Auxiliary VT 1 Connection
0 to 6
---
1
F166
1 (Vag)
4505
Auxiliary VT 1 Secondary
25 to 240
V
0.1
F001
664
4506
Auxiliary VT 1 Ratio
1 to 24000
:1
1
F060
1
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
0 to 1
---
---
F206
“SRC 1"
4583
Source 1 Phase CT
0 to 63
---
1
F400
0
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
Table B–9: MODBUS MEMORY MAP (Sheet 24 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...