GE Multilin
L90 Line Current Differential System
5-133
5 SETTINGS
5.5 FLEXLOGIC
5
ELEMENT:
Open pole detector
OPEN POLE OP
Ф
A
OPEN POLE OP
Ф
B
OPEN POLE OP
Ф
C
OPEN POLE BKR
Ф
A OP
OPEN POLE BKR
Ф
B OP
OPEN POLE BKR
Ф
C OP
OPEN POLE BLK N
OPEN POLE BLK AB
OPEN POLE BLK BC
OPEN POLE BLK CA
OPEN POLE REM OP
Ф
A
OPEN POLE REM OP
Ф
B
OPEN POLE REM OP
Ф
C
OPEN POLE OP
OPEN POLE I<
Ф
A
OPEN POLE I<
Ф
B
OPEN POLE I<
Ф
C
Open pole condition is detected in phase A
Open pole condition is detected in phase B
Open pole condition is detected in phase C
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase A
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase B
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase C
Blocking signal for neutral, ground, and negative-sequence overcurrent
element is established
Blocking signal for the AB phase distance elements is established
Blocking signal for the BC phase distance elements is established
Blocking signal for the CA phase distance elements is established
Remote open pole condition detected in phase A
Remote open pole condition detected in phase B
Remote open pole condition detected in phase C
Open pole detector is operated
Open pole undercurrent condition is detected in phase A
Open pole undercurrent condition is detected in phase B
Open pole undercurrent condition is detected in phase C
ELEMENT:
Overfrequency
OVERFREQ 1 PKP
OVERFREQ 1 OP
OVERFREQ 1 DPO
Overfrequency 1 has picked up
Overfrequency 1 has operated
Overfrequency 1 has dropped out
OVERFREQ 2 to 4
Same set of operands as shown for OVERFREQ 1
ELEMENT:
Synchrophasor
phasor data
concentrator
PDC NETWORK CNTRL 1
PDC NETWORK CNTRL 2
PDC NETWORK CNTRL 16
Phasor data concentrator asserts control bit 1 as received via the network
Phasor data concentrator asserts control bit 2 as received via the network
Phasor data concentrator asserts control bit 16 as received via the network
ELEMENT:
Phase directional
overcurrent
PH DIR1 BLK A
PH DIR1 BLK B
PH DIR1 BLK C
PH DIR1 BLK
Phase A directional 1 block
Phase B directional 1 block
Phase C directional 1 block
Phase directional 1 block
PH DIR2
Same set of operands as shown for PH DIR1
ELEMENT:
Phase distance
PH DIST Z1 PKP
PH DIST Z1 OP
PH DIST Z1 OP AB
PH DIST Z1 OP BC
PH DIST Z1 OP CA
PH DIST Z1 PKP AB
PH DIST Z1 PKP BC
PH DIST Z1 PKP CA
PH DIST Z1 SUPN IAB
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
PH DIST Z1 DPO AB
PH DIST Z1 DPO BC
PH DIST Z1 DPO CA
Phase distance zone 1 has picked up
Phase distance zone 1 has operated
Phase distance zone 1 phase AB has operated
Phase distance zone 1 phase BC has operated
Phase distance zone 1 phase CA has operated
Phase distance zone 1 phase AB has picked up
Phase distance zone 1 phase BC has picked up
Phase distance zone 1 phase CA has picked up
Phase distance zone 1 phase AB IOC is supervising
Phase distance zone 1 phase BC IOC is supervising
Phase distance zone 1 phase CA IOC is supervising
Phase distance zone 1 phase AB has dropped out
Phase distance zone 1 phase BC has dropped out
Phase distance zone 1 phase CA has dropped out
PH DIST Z2 to Z3
Same set of operands as shown for PH DIST Z1
ELEMENT:
Phase
instantaneous
overcurrent
PHASE IOC1 PKP
PHASE IOC1 OP
PHASE IOC1 DPO
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
At least one phase of phase instantaneous overcurrent 1 has picked up
At least one phase of phase instantaneous overcurrent 1 has operated
All phases of phase instantaneous overcurrent 1 have dropped out
Phase A of phase instantaneous overcurrent 1 has picked up
Phase B of phase instantaneous overcurrent 1 has picked up
Phase C of phase instantaneous overcurrent 1 has picked up
Phase A of phase instantaneous overcurrent 1 has operated
Phase B of phase instantaneous overcurrent 1 has operated
Phase C of phase instantaneous overcurrent 1 has operated
Phase A of phase instantaneous overcurrent 1 has dropped out
Phase B of phase instantaneous overcurrent 1 has dropped out
Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 and higher
Same set of operands as shown for PHASE IOC1
Table 5–12: L90 FLEXLOGIC OPERANDS (Sheet 5 of 11)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...