5-176
L90 Line Current Differential System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–82: GROUND DISTANCE ZONE 1 SCHEME LOGIC
837007AH.CDR
AND
AND
AND
OR
Quadrilateral
characteristic
only
AND
OR
MEMORY
V_1 > 0.80 pu
I_1 > 0.025 pu
SETTING
Enabled = 1
GND DIST Z1 FUNCTION
SETTING
Off = 0
GND DIST Z1 BLK
SETTING
IA
IB
DISTANCE SOURCE
IC
VAG
VBG
VCG
V_1
I_1
W
ye
V
Ts
SETTINGS
GND DIST Z1 ZOM/Z1 ANG
RUN
A ELEMENT
RUN
B ELEMENT
RUN
C ELEMENT
GND DIST Z1 POL CURRENT
GND DIST Z1 NON-HOMGEN ANG
GND DIST Z1 COMP LIMIT
GND DIST Z1 DIR RCA
GND DIST Z1 DIR COMP LIMIT
GND DIST Z1 VOLT LEVEL
GND DIST Z1 QUAD RGT BLD
GND DIST Z1 QUAD RGT BLD RCA
GND DIST Z1 QUAD LFT BLD
GND DIST Z1 QUAD LFT BLD RCA
TIMER
1 cycle
1 cycle
SETTING
GND DIST Z1 SUPV
RUN
| IN – 0.05 × I_1 | > Pickup
FLEXLOGIC OPERANDS
GND DIST Z1 PKP A
GND DIST Z1 DPO A
FLEXLOGIC OPERANDS
GND DIST Z1 PKP B
GND DIST Z1 DPO B
FLEXLOGIC OPERANDS
GND DIST Z1 PKP C
GND DIST Z1 DPO C
FLEXLOGIC OPERAND
GND DIST Z1 PKP
FLEXLOGIC OPERANDS
OPEN POLE OP ФA
OPEN POLE OP ФB
OPEN POLE OP ФC
D60, L60, and L90 only
GND DIST Z1 SUPN IN
FLEXLOGIC OPERAND
IN
I_2
I_0
GND DIST Z1 REV REACH
GND DIST Z1 REV REACH RCA
GND DIST Z1 REACH
GND DIST Z1 RCA
GND DIST Z1 ZOM/Z1 MAG
GND DIST Z1 Z0/Z1 ANG
GND DIST Z1 Z0/Z1 MAG
GND DIST Z1 SHAPE
GND DIST Z1 DIR
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...