6-20
L90 Line Current Differential System
GE Multilin
6.3 METERING
6 ACTUAL VALUES
6
The metered values for current and power demand are displayed in this menu. The "SRC 1" text will be replaced by what-
ever name was programmed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL
SOURCES
).
The relay measures (absolute values only) the source demand on each phase and average three phase demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier demand penalties or for statistical
metering purposes. Demand calculations are based on the measurement type selected in the
SETTINGS
PRODUCT SETUP
DEMAND
menu. For each quantity, the relay displays the demand over the most recent demand time interval, the maxi-
mum demand since the last maximum demand reset, and the time and date stamp of this maximum demand value. Maxi-
mum demand quantities can be reset to zero with the
CLEAR RECORDS
CLEAR DEMAND RECORDS
command.
i) FREQUENCY METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
).
SOURCE FREQUENCY
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
POWER SYSTEM
settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
If the 87L function is enabled, then dedicated 87L frequency tracking is engaged. In this case, the relay uses the
METERING
TRACKING FREQUENCY
TRACKING FREQUENCY
value for all computations, overriding the
SOURCE FREQUENCY
value.
MESSAGE
SRC 1 DMD IC MAX:
0.000 A
MESSAGE
SRC 1 DMD IC DATE:
2001/07/31 16:30:07
MESSAGE
SRC 1 DMD W:
0.000 W
MESSAGE
SRC 1 DMD W MAX:
0.000 W
MESSAGE
SRC 1 DMD W DATE:
2001/07/31 16:30:07
MESSAGE
SRC 1 DMD VAR:
0.000 var
MESSAGE
SRC 1 DMD VAR MAX:
0.000 var
MESSAGE
SRC 1 DMD VAR DATE:
2001/07/31 16:30:07
MESSAGE
SRC 1 DMD VA:
0.000 VA
MESSAGE
SRC 1 DMD VA MAX:
0.000 VA
MESSAGE
SRC 1 DMD VA DATE:
2001/07/31 16:30:07
FREQUENCY
SRC 1
SRC 1 FREQUENCY:
0.00 Hz
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...