L90 Line Current Differential System
6-27
6 ACTUAL VALUES
6.4 RECORDS
6
PATH: ACTUAL VALUES
RECORDS
PMU RECORDS
PMU 1 RECORDING
6.4.6 BREAKER MAINTENANCE
PATH: ACTUAL VALUES
RECORDS
MAINTENANCE
BREAKER 1(4)
There is an identical menu for each of the breakers. The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing breaker arcing current records. The
BREAKER OPERATING TIME
is
defined as the slowest operating time of breaker poles that were initiated to open.
PMU 1
RECORDING
PMU 1 FORCE TRIGGER:
Yes
Range: No, Yes
MESSAGE
PUM 1 AVAILABLE
RECORDS: 0
Range: 0 to 65535 in steps of 1
MESSAGE
PUM 1 SECONDS
PER RECORD: 0.0
Range: 0 to 6553.5 in steps of 0.1
MESSAGE
PUM 1 LAST CLEARED:
2005/07/14 015:40:16
Range: date and time in format shown
BREAKER 1
BKR 1 ARCING AMP
A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
A: 0
ms
MESSAGE
BKR 1 OPERATING TIME
B: 0
ms
MESSAGE
BKR 1 OPERATING TIME
C: 0
ms
MESSAGE
BKR 1 OPERATING
TIME:
0 ms
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...