GE Multilin
L90 Line Current Differential System
B-57
APPENDIX B
B.4 MEMORY MAPPING
B
FlexElement Actuals (Read Only) (16 modules)
9000
FlexElement 1 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9902
FlexElement 2 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9904
FlexElement 3 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9906
FlexElement 4 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9908
FlexElement 5 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
990A
FlexElement 6 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
990C
FlexElement 7 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
990E
FlexElement 8 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
Breaker Restrike (Read/Write Setting) (3 modules)
9930
Breaker restrike 1 function
0 to 1
---
1
F102
0 (Disabled)
9931
Breaker restrike 1 block
0 to 4294967295
---
1
F300
0
9933
Breaker restrike 1 signal source
0 to 5
---
1
F167
0 (SRC 1)
9934
Breaker restrike 1 pickup
0.10 to 2.00
pu
0.01
F001
500
9935
Breaker restrike 1 reset delay
0 to 65.535
s
0.001
F001
100
9936
Breaker restrike 1 HF detect
0 to 1
---
1
F102
1 (Enabled)
9937
Breaker restrike 1 breaker open
0 to 4294967295
---
1
F300
0
9939
Breaker restrike 1 open command
0 to 4294967295
---
1
F300
0
993B
Breaker restrike 1 close command
0 to 4294967295
---
1
F300
0
993D
Breaker restrike 1 target
0 to 2
---
1
F109
0 (Self-reset)
993E
Breaker restrike 1 events
0 to 1
---
1
F102
0 (Disabled)
993F
Reserved (2 items)
0 to 1
---
1
F001
0
9941
...Repeated for breaker restrike 2
VT Fuse Failure (Read/Write Setting) (6 modules)
A09A
VT Fuse Failure Function
0 to 1
---
1
F102
0 (Disabled)
A09B
VT Fuse Failure Neutral Wire Open Function
0 to 1
---
1
F102
0 (Disabled)
A09C
VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup
0 to 3
pu
0.001
F001
100
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
A0A6
...Repeated for module number 5
A0A9
...Repeated for module number 6
A0AC
VTFF x V0 3rd harmonic
0 to 999999.999
V
0.001
F060
0
Selector switch actual values (read only)
A210
Selector switch 1 position
1 to 7
---
1
F001
0
A211
Selector switch 2 position
1 to 7
---
1
F001
1
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 4294967295
---
1
F300
0
A285
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A286
Selector 1 Acknowledge
0 to 4294967295
---
1
F300
0
A288
Selector 1 Bit0
0 to 4294967295
---
1
F300
0
A28A
Selector 1 Bit1
0 to 4294967295
---
1
F300
0
A28C
Selector 1 Bit2
0 to 4294967295
---
1
F300
0
A28E
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28F
Selector 1 Bit Acknowledge
0 to 4294967295
---
1
F300
0
A291
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A292
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A293
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A294
Reserved (10 items)
---
---
1
F001
0
A29E
...Repeated for Selector 2
Table B–9: MODBUS MEMORY MAP (Sheet 49 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...