B-64
L90 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
B24C
...Repeated for Received Analog 31
B24E
...Repeated for Received Analog 32
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290
IEC 61850 configurable reports dataset items (64 items)
0 to 848
---
1
F615
0 (None)
Wattmetric ground fault settings (read/write grouped, 2 modules)
B300
Wattmetric ground fault 1 function
0 to 1
---
1
F102
0 (Disabled)
B301
Wattmetric ground fault 1 source
0 to 5
---
1
F167
0 (SRC 1)
B302
Wattmetric ground fault 1 voltage
0 to 1
---
1
F234
0 (Calculated VN)
B303
Wattmetric ground fault 1 overvoltage pickup
0.02 to 3.00
pu
0.01
F001
20
B304
Wattmetric ground fault 1 current
0 to 1
---
1
F235
(Calculated IN)
B305
Wattmetric ground fault 1 overcurrent pickup
0.002 to 30.000
pu
0.001
F001
60
B306
Wattmetric ground fault 1 overcurrent pickup delay
0 to 600
s
0.01
F001
20
B307
Wattmetric ground fault 1 power pickup
0.001 to 1.2
pu
0.001
F001
100
B308
Wattmetric ground fault 1 ECA
0 to 360
° Lag
1
F001
0
B309
Wattmetric ground fault 1 power pickup delay
0 to 600
s
0.01
F001
20
B30A
Wattmetric ground fault 1 curve
0 to 5
---
1
F236
0 (Definite Time)
B30B
Wattmetric ground fault 1 multiplier
0.01 to 2
s
0.01
F001
100
B30C
Wattmetric ground fault 1 block
0 to 65535
---
1
F300
0
B30E
Wattmetric ground fault 1 target
0 to 2
---
1
F109
0 (Self-reset)
B30F
Wattmetric ground fault 1 events
0 to 1
---
1
F102
0 (Disabled)
B310
Wattmetric ground fault 1 reference power
0.001 to 1.2
pu
0.001
F001
500
B311
Wattmetric ground fault x Reserved
0 to 1
---
1
F001
0
B312
...Repeated for wattmetric ground fault 2
B324
...Repeated for wattmetric ground fault 3
B336
...Repeated for wattmetric ground fault 4
B348
...Repeated for wattmetric ground fault 5
Wattmetric ground fault actual values (read only) (5 modules)
B360
Wattmetric ground fault 1 operating power
0 to 999999.999
W
0.001
F060
0
B362
...Repeated for wattmetric ground fault 2
B364
...Repeated for wattmetric ground fault 3
B366
...Repeated for wattmetric ground fault 4
B368
...Repeated for wattmetric ground fault 5
IEC 61850 XSWI Configuration (Read/Write Setting) (24 modules)
B370
Flexlogic Operand for IEC 61850 XSWI.ST.Loc Status
0 to 4294967295
---
1
F300
0
IEC 61850 XSWI Configuration (Read/Write Command) (24 modules)
B372
Command to Clear XSWI OpCnt (Operation Counter)
0 to 1
---
1
F126
0 (No)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B400
Number of Status Indications in GGIO1
8 to 128
---
8
F001
8
B402
IEC 61850 GGIO1 Indication FlexLogic operands (128
items)
0 to 4294967295
---
1
F300
0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0
IEC 61850 Configurable GOOSE Function
0 to 1
---
1
F102
0 (None)
B5A1
IEC 61850 Configurable GOOSE ID
---
---
---
F209
“GOOSEOut_x_”
B5C2
Configurable GOOSE Destination MAC Address
---
---
---
F072
0
B5C5
IEC 61850 Configurable GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B5C6
IEC 61850 Configurable GOOSE VLAN ID
0 to 4095
---
1
F001
0
B5C7
IEC 61850 Configurable GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B5C8
IEC 61850 Configurable GOOSE ConfRev
1 to 4294967295
---
1
F003
1
B5CA
IEC 61850 Configurable GOOSE Retransmission Curve
0 to 3
---
1
F611
3 (Relaxed)
B5CB
Configurable GOOSE dataset items for transmission
(64 items)
0 to 542
---
1
F616
0 (None)
B60B
...Repeated for Module 2
B676
...Repeated for Module 3
B6E1
...Repeated for Module 4
B74C
...Repeated for Module 5
Table B–9: MODBUS MEMORY MAP (Sheet 56 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...