UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
66E5
Third Harmonic Neutral Undervoltage
Target
0 to 2
---
1
F109
0 (Self-reset)
"
66E6
Third Harmonic Neutral Undervoltage
Events
0 to 1
---
1
F102
0 (Disabled)
"
66E7
Reserved (4 items)
0 to 65535
---
1
F001
0
Generator Unbalance (Read/Write Grouped Setting)
G30, G60
66F0
Generator Unbalance Function
0 to 1
---
1
F102
0 (Disabled)
"
66F1
Generator Unbalance Source
0 to 5
---
1
F167
0 (SRC 1)
"
66F2
Generator Unbalance Inom (rated full load
current of the machine)
0 to 1.25
pu
0.001 F001
800
"
66F3
Generator Unbalance Stage 1 Pickup
0 to 100
%
0.01
F001
800
"
66F4
Generator Unbalance Stage 1 K value
0 to 100
---
0.01
F001
100
"
66F5
Generator Unbalance Stage 1 Tmin
0 to 50
s
0.001 F001
250
"
66F6
Generator Unbalance Stage 1 Tmax
0 to 1000
s
0.1
F001
6000
"
66F7
Generator Unbalance Stage 1 K Reset
0 to 1000
s
0.1
F001
2400
"
66F8
Generator Unbalance Stage 2 Pickup
0 to 100
%
0.01
F001
300
"
66F9
Generator Unbalance Stage 2 Pickup Delay 0 to 1000
s
0.1
F001
50
"
66FA
Generator Unbalance Block
0 to 4294967295
---
1
F300
0
"
66FC
Generator Unbalance Target
0 to 2
---
1
F109
0 (Self-reset)
"
66FD
Generator Unbalance Events
0 to 1
---
1
F102
0 (Disabled)
"
66FE
Reserved (3 items)
0 to 65535
---
1
F001
0
Stator Ground Source (Read/Write Grouped Setting)
G30, G60
670A
Stator Ground Source
0 to 5
---
1
F167
0 (SRC 1)
Subharmonic Stator Ground (Read/Write Grouped Setting)
G60
6710
Subharmonic Stator Ground Function
0 to 1
---
1
F102
0 (Disabled)
"
6711
Subharmonic Stator Ground Stage 1 Pickup 1 to 20
kOhm
1
F001
10
"
6712
Subharmonic Stator Ground Stage 1 Pickup
Delay
0.1 to 600
s
0.1
F001
100
"
6713
Subharmonic Stator Ground Stage 2 Pickup 1 to 20
kOhm
1
F001
3
"
6714
Subharmonic Stator Ground Stage 2 Pickup
Delay
0.1 to 600
s
0.1
F001
10
"
6715
Subharmonic CT Angle Compensation
-30 to 30
degrees 0.1
F002
0
"
6718
Subharmonic Stator Ground OC Pickup
0.001 to 1
pu
0.001 F001
10
"
6719
Subharmonic Stator Ground OC Delay
0.01 to 600
s
0.01
F001
100
"
671A
Subharmonic Stator Ground Volt Supv
0 to 0.1
pu
0.001 F001
0
"
671B
Subharmonic Stator Ground Curr Supv
0 to 0.1
pu
0.001 F001
0
"
671C
Subharmonic Stator Ground Block
0 to 4294967295
---
---
F300
0
"
671E
Subharmonic Stator Ground Events
0 to 1
---
1
F102
0 (Disabled)
"
671F
Subharmonic Stator Ground Target
0 to 2
---
1
F109
0 (Self-reset)
Stator Ground (Read/Write Grouped Setting)
G30, G60
6720
Stator Ground Function
0 to 1
---
1
F102
0 (Disabled)
"
6721
Stator Ground Stage 1 Pickup
0 to 0.9
pu
0.001 F001
150
"
6722
Stator Ground Stage 1 Pickup Delay
0 to 600
s
0.01
F001
100
"
6723
Stator Ground Stage 1 Supv
0.001 to 0.1
pu
0.000
1
F001
57
"
6724
Stator Ground Stage 2 Pickup
0 to 0.9
pu
0.001 F001
150
"
6725
Stator Ground Stage 2 Pickup Delay
0 to 600
s
0.01
F001
0
"
6726
Stator Ground Stage 2 Supv
0.001 to 0.1
pu
0.000
1
F001
45
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...