2-94
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
7075
...Repeated for Breaker Failure 14
"
707E
...Repeated for Breaker Failure 15
"
7087
...Repeated for Breaker Failure 16
"
7090
...Repeated for Breaker Failure 17
"
7099
...Repeated for Breaker Failure 18
"
70A2
...Repeated for Breaker Failure 19
"
70AB
...Repeated for Breaker Failure 20
"
70B4
...Repeated for Breaker Failure 21
"
70BD
...Repeated for Breaker Failure 22
"
70C6
...Repeated for Breaker Failure 23
"
70CF
...Repeated for Breaker Failure 24
Phase Undervoltage (Read/Write Grouped Setting) (3 Modules)
All except B90,
C30, T35
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
"
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001 F001
1000
"
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite
Time)
"
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
"
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001 F001
100
"
7006
Phase Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
"
7008
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7009
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
700A
Phase Undervoltage 1 Measurement Mode 0 to 1
---
1
F186
0 (Phase to
Ground)
"
700B
Reserved (6 items)
0 to 1
---
1
F001
0
"
7013
...Repeated for Phase Undervoltage 2
"
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)
C60, C70, D30,
D60, F60, G30,
G60, L30, L60,
L90, M60, N60,
T60
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001 F001
1000
"
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
"
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
"
7045
Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
"
7047
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7048
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
7049
...Repeated for Phase Overvoltage 2
"
7052
...Repeated for Phase Overvoltage 3
Phase Distance (Read/Write Grouped Setting) (3 or 5 Modules)
D30, D60, G60,
L60, L90, T60
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7071
Phase Distance Zone 1 Current Supervision 0.05 to 30
pu
0.001 F001
200
"
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
"
7073
Phase Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...