2-102
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
7705
Time Overcurrent 1 Reset
0 to 1
---
1
F104
0
(Instantaneo
us)
"
7706
Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
"
7708
Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7709
Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
770A
Reserved (2 items)
0 to 65535
---
1
F001
0
"
770C
...Repeated for Time Overcurrent 2
"
7718
...Repeated for Time Overcurrent 3
"
7724
...Repeated for Time Overcurrent 4
"
7730
...Repeated for Time Overcurrent 5
"
773C
...Repeated for Time Overcurrent 6
"
7748
...Repeated for Time Overcurrent 7
"
7754
...Repeated for Time Overcurrent 8
"
7760
...Repeated for Time Overcurrent 9
"
776C
...Repeated for Time Overcurrent 10
"
7778
...Repeated for Time Overcurrent 11
"
7784
...Repeated for Time Overcurrent 12
"
7790
...Repeated for Time Overcurrent 13
"
779C
...Repeated for Time Overcurrent 14
"
77AB
...Repeated for Time Overcurrent 15
"
77B4
...Repeated for Time Overcurrent 16
"
77C0
...Repeated for Time Overcurrent 17
"
77CC
...Repeated for Time Overcurrent 18
"
77D8
...Repeated for Time Overcurrent 19
"
77E4
...Repeated for Time Overcurrent 20
"
77F0
...Repeated for Time Overcurrent 21
"
77FC
...Repeated for Time Overcurrent 22
"
7808
...Repeated for Time Overcurrent 23
"
7814
...Repeated for Time Overcurrent 24
Thermal Overload Protection (Read/Write Settings) (2 Modules)
All except B90,
C30, M60
7788
Thermal Protection 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
7789
Thermal Protection 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
778A
Thermal Protection 1 Base Current
0.2 to 3
pu
0.01
F001
80
"
778B
Thermal Protection 1 K Factor
1 to 1.2
---
0.05
F001
110
"
778C
Thermal Protection 1 Trip Time Constant
0 to 1000
min.
1
F001
45
"
778D
Thermal Protection 1 Reset Time Constant 0 to 1000
min.
1
F001
45
"
778E
Thermal Protection 1 Minimum Reset Time 0 to 1000
min.
1
F001
20
"
778F
Thermal Protection 1 Reset
0 to 4294967295
---
1
F300
0
"
7791
Thermal Protection 1 Block
0 to 4294967295
---
1
F300
0
"
7793
Thermal Protection 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
7794
Thermal Protection 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
7795
Reserved (2 items)
---
---
---
F001
0
"
7797
Repeated for Thermal Protection 2
Broken Conductor Detection (Read/Write Settings) (2, 4, or 6 Modules)
D30, D60, F35,
F60, L30, L90
77AA
Broken Conductor 1 Function
0 to 1
---
1
F102
0 (Disabled)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...