CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-105
2
"
7B03
Thermal Model Bias K Factor
0 to 19
---
1
F001
0
"
7B04
Thermal Model Time Constant Running
1 to 65000
min
1
F001
15
"
7B05
Thermal Model Time Constant Stopped
1 to 65000
min
1
F001
30
"
7B06
Thermal Model Hot Cold Ratio
0.01 to 1
---
0.01
F001
100
"
7B07
Thermal Model RTD Bias
0 to 1
---
1
F102
0 (Disabled)
"
7B08
Thermal Model RTD Bias Minimum
0 to 250
°C
1
F001
40
"
7B09
Thermal Model RTD Bias Center
0 to 250
°C
1
F001
130
"
7B0A
Thermal Model RTD Bias Maximum
0 to 250
°C
1
F001
155
"
7B0B
Thermal Model Start Inhibit Margin
0 to 25
%
1
F001
0
"
7B0C
Thermal Model Block
0 to 4294967295
---
1
F300
0
"
7B0E
Thermal Model Events
0 to 1
---
1
F102
0 (Disabled)
"
7B0F
Thermal Model Target
0 to 2
---
1
F109
0 (Self-reset)
"
7B10
Thermal Model Curve Effect
0 to 1
---
1
F096
0 (Cutoff)
"
7B11
Speed 2 Thermal Model Curve
0 to 5
---
1
F099
0 (Motor)
"
7B12
Speed 2 Thermal Model TD Multiplier
0 to 600
---
0.01
F001
100
"
7B13
Reserved
0 to 600
---
0.01
F001
100
"
7B14
Thermal Model IEC Curve K Factor
1 to 1.5
---
0.05
F001
110
"
7B15
Thermal Model IEC Curve Time Constant
0 to 1000
min.
1
F001
45
Voltage Dependent Overload (Read/Write Grouped Setting)
M60
7B20
Voltage Dependent Overload Function
0 to 1
---
1
F102
0 (Disabled)
"
7B21
Voltage Dependent Overload Minimum
Motor Volts
60 to 99
%
1
F001
80
"
7B22
Voltage Dependent Overload Voltage Loss 0 to 4294967295
---
1
F300
0
"
7B24
VD Overload Stall Current at Minimum Volts 1.5 to 20
×
FLA
0.01
F001
450
"
7B25
VD Overload Safe Stall Time at Minimum
Volts
0.1 to 1000
s
0.1
F001
200
"
7B26
VD Overload Acceleration Intersect at
Minimum Volts
1.5 to 20
×
FLA
0.01
F001
400
"
7B27
VD Overload Stall Current at 100% Voltage 1.5 to 20
×
FLA
0.01
F001
600
"
7B28
VD Overload Safe Stall Time at 100%
Voltage
0.1 to 1000
s
0.1
F001
100
"
7B29
VD Overload Acceleration Intersect at
100% Voltage
1.5 to 20
×
FLA
0.01
F001
500
"
7B2A
Speed 2 Voltage Dependent Overload
Function
0 to 1
---
1
F102
0 (Disabled)
"
7B2B
Speed 2 VD Overload Minimum Motor Volts 60 to 99
%
1
F001
80
"
7B2C
Speed 2 Voltage Dependent Overload
Voltage Loss
0 to 4294967295
---
1
F300
0
"
7B2E
Speed 2 VD Overload Stall Current at
Minimum Volts
1.5 to 20
×
FLA
0.01
F001
450
"
7B2F
Speed 2 VD Overload Safe Stall Time at
Minimum Volts
0.1 to 1000
s
0.1
F001
200
"
7B30
Speed 2 VD Acceleration Intersect at
Minimum Volts
1.5 to 20
×
FLA
0.01
F001
400
"
7B31
Speed 2 VD Overload Stall Current at 100%
Voltage
1.5 to 20
×
FLA
0.01
F001
600
"
7B32
Speed 2 VD Overload Safe Stall Time at
100% Voltage
0.1 to 1000
s
0.1
F001
200
"
7B33
Speed 2 VD Acceleration Intersect at 100%
Voltage
1.5 to 20
×
FLA
0.01
F001
500
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...