CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-113
2
EGD Slow Production Status (Read Only and Read Only Non-Volatile) (2 Modules)
B30, C30, C60,
F35, F60, G30,
G60, M60, T35,
T60
83F0
EGD Slow Producer Exchange 1 Signature
0 to 65535
---
1
F001
0
"
83F1
EGD Slow Producer Exchange 1
Configuration Time
0 to 4294967295
---
---
F003
0
"
83F3
EGD Slow Producer Exchange 1 Size
0 to 65535
---
1
F001
0
"
83F4
...Repeated for EGD Slow Producer
Exchange 2
EGD Fast Production (Read/Write Setting)
B30, C30, C60,
F35, F60, G30,
G60, M60, T35,
T60
8400
EGD Fast Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
8401
EGD Fast Producer Exchange 1 Destination 0 to 4294967295
---
1
F003
0
"
8403
EGD Fast Producer Exchange 1 Data Rate
50 to 1000
ms
50
F001
1000
"
8404
EGD Fast Producer Exchange 1 Data Item 1
(20 items)
0 to 65535
---
1
F001
0
"
8418
Reserved (80 items)
---
---
---
F001
0
EGD Slow Production (Read/Write Setting) (2 Modules)
B30, C30, C60,
F35, F60, G30,
G60, M60, T35,
T60
8468
EGD Slow Producer Exchange 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
8469
EGD Fast Producer Exchange 1 Destination 0 to 4294967295
---
1
F003
0
"
846B
EGD Slow Producer Exchange 1 Data Rate 500 to 1000
ms
50
F001
1000
"
846C
EGD Slow Producer Exchange 1 Data Item
1 (50 items)
0 to 65535
---
1
F001
0
"
849E
Reserved (50 items)
---
---
---
F001
0
"
84D0
...Repeated for EGD Slow Producer
Exchange 2
Direct Integers (Read/Write Setting) (16 Modules)
N60
8540
Direct Integer Output 1 Value
0 to 65535
---
1
F612
0
"
8541
Direct Integer Output 1 Trigger
0 to 4294967295
---
1
F300
0
"
8543
Direct Integer Input 1 Device
0 to 16
---
1
F001
0
"
8544
Direct Integer Input 1 Number
0 to 16
---
1
F001
0
"
8545
Direct Integer Input 1 Default Value
0 to 4294967295
---
1
F003
1000
"
8547
Direct Integer Input 1 Mode
0 to 1
---
1
F491
0 (Default
Value)
"
8548
Direct Integer Reserved
0 to 65535
---
1
F003
0
"
854A
...Repeated for Direct Integer Output 2
"
8554
...Repeated for Direct Integer Output 3
"
855E
...Repeated for Direct Integer Output 4
"
8568
...Repeated for Direct Integer Output 5
"
8572
...Repeated for Direct Integer Output 6
"
857C
...Repeated for Direct Integer Output 7
"
8586
...Repeated for Direct Integer Output 8
"
8590
...Repeated for Direct Integer Output 9
"
859A
...Repeated for Direct Integer Output 10
"
85A4
...Repeated for Direct Integer Output 11
"
85AE
...Repeated for Direct Integer Output 12
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...