2-124
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
Automatic Voltage Regulator Settings (Read/Write) (3 Modules)
C70
9C90
Automatic Voltage Regulator 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
9C91
Automatic Voltage Regulator 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
9C92
Automatic Voltage Regulator 1 Minimum
Voltage
0.500 to 1.500
pu
0.001 F001
500
"
9C93
Automatic Voltage Regulator 1 Control
Mode
0 to 1
---
1
F536
0 (Voltage)
"
9C94
Automatic Voltage Regulator 1 Voltage
Operating Signal
0 to 8
---
1
F535
4 (V1)
"
9C95
Automatic Voltage Regulator 1 Voltage
Level to Close
0.750 to 1.500
pu
0.001 F001
950
"
9C96
Automatic Voltage Regulator 1 Voltage
Level to Open
0.750 to 1.500
pu
0.001 F001
1050
"
9C97
AVR 1 Voltage Drop Compensation
Impedance
0 to 250
ohms
0.01
F001
0
"
9C98
AVR 1 Voltage Drop Compensation RCA
30 to 90
°
1
F001
75
"
9C99
Automatic Voltage Regulator 1 VAR Level to
Close
–1.500 to 1.500
pu
0.001 F002
950
"
9C9A
Automatic Voltage Regulator 1 VAR Level to
Open
–1.500 to 1.500
pu
0.001 F002
1050
"
9C9B
Automatic Voltage Regulator 1 Power
Factor Limit
0.50 to 1.00
---
0.01
F001
100
"
9C9C
Automatic Voltage Regulator 1 VAR Open
Mode
0 to 1
---
1
F537
1 (Minimize
no. of ops.)
"
9C9D
Automatic Voltage Regulator 1 Delay
Before Close
0 to 65.535
s
0.001 F001
1000
"
9C9E
Automatic Voltage Regulator 1 Delay
Before Open
0 to 65.535
s
0.001 F001
1000
"
9C9F
Automatic Voltage Regulator 1 Block
0 to 4294967295
---
1
F300
0
"
9CA1
Automatic Voltage Regulator 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
9CA2
Automatic Voltage Regulator 1 Target
0 to 2
---
1
F109
0 (Self-Reset)
"
9CA3
Automatic Voltage Regulator 1 Reserved
0 to 0.001
---
0.001 F001
0
"
9CA4
...Repeated for Automatic Voltage
Regulator 2
"
9CB8
...Repeated for Automatic Voltage
Regulator 3
Neutral Current Unbalance Settings (Read/Write Grouped Setting) (3 Modules)
C70
9CE0
Neutral Current Unbalance 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
9CE1
Neutral Current Unbalance 1 Bank Source 0 to 5
---
1
F167
0 (SRC 1)
"
9CE2
Neutral Current Unbalance 1
k
Magnitude 0 to 0.1500
---
0.000
1
F001
0
"
9CE3
Neutral Current Unbalance 1
k
Angle
0 to 359
°
1
F001
0
"
9CE4
Neutral Current Unbalance 1 Stage 1
Pickup
0 to 5.000
pu
0.001 F001
20
"
9CE5
Neutral Current Unbalance 1 Stage 1 Slope 0 to 10.0
%
0.1
F001
20
"
9CE6
Neutral Current Unbalance 1 Stage 2
Pickup
0 to 5.000
pu
0.001 F001
30
"
9CE7
Neutral Current Unbalance 1 Stage 2 Slope 0 to 10.0
%
0.1
F001
20
"
9CE8
Neutral Current Unbalance 1 Stage 3
Pickup
0 to 5.000
pu
0.001 F001
40
"
9CE9
Neutral Current Unbalance 1 Stage 3 Slope 0 to 10.0
%
0.1
F001
20
"
9CEA
Neutral Current Unbalance 1 Stage 4
Pickup
0 to 5.000
pu
0.001 F001
50
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...