CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-129
2
"
A029
Motor Load Deviation at Broken Rotor Bar
Maximum
0 to 1.5
× FLA
0.01
F001
0
"
A02A
Time Stamp at Broken Rotor Bar Maximum 0 to 4294967295
---
1
F050
0
Broken Rotor Bar Commands (Read/Write Commands)
M60
A02D
Broken Rotor Bar Clear Data Command
0 to 1
---
1
F126
0 (No)
Broken Rotor Bar Detection (Read/Write Settings)
M60
A030
Broken Rotor Bar Function
0 to 1
---
1
F102
0 (Disabled)
"
A031
Start of Broken Rotor Bar Offset
–12 to 11.99
Hz
0.01
F002
40
"
A032
End of Broken Rotor Bar Offset
–11.99 to 12
Hz
0.01
F002
200
"
A033
Broken Rotor Bar Start Block Delay
0 to 600
s
0.01
F001
6000
"
A034
Minimum Motor Load
0.5 to 1
× FLA
0.01
F001
70
"
A035
Maximum Load Deviation
0 to 1
× FLA
0.01
F001
10
"
A036
Maximum Current Unbalance
0 to 100
%
0.1
F001
150
"
A037
Broken Rotor Bar Pickup
–60 to –12
dB
1
F002
-40
"
A038
Broken Rotor Bar Reset Delay
0 to 600
s
0.01
F001
0
"
A039
Broken Rotor Bar Block
0 to 4294967295
---
1
F300
0
"
A03B
Broken Rotor Bar Target
0 to 2
---
1
F109
0 (Self-reset)
"
A03C
Broken Rotor Bar Events
0 to 1
---
1
F102
0 (Disabled)
Pilot Permissive Overreach Transfer Trip (POTT) Settings (Read/Write)
L60
A070
POTT Scheme Function
0 to 1
---
1
F102
0 (Disabled)
"
A071
POTT Permissive Echo
0 to 1
---
1
F102
0 (Disabled)
"
A072
POTT Rx Pickup Delay
0 to 65.535
s
0.001 F001
0
"
A073
POTT Transient Block Pickup Delay
0 to 65.535
s
0.001 F001
20
"
A074
POTT Transient Block Reset Delay
0 to 65.535
s
0.001 F001
90
"
A075
POTT Echo Duration
0 to 65.535
s
0.001 F001
100
"
A076
POTT Line End Open Pickup Delay
0 to 65.535
s
0.001 F001
50
"
A077
POTT Seal In Delay
0 to 65.535
s
0.001 F001
400
"
A078
POTT Ground Direction OC Forward
0 to 4294967295
---
1
F300
0
"
A07A
POTT Rx
0 to 4294967295
---
1
F300
0
"
A07C
POTT Echo Lockout
0 to 65.535
s
0.001 F001
250
"
A07D
POTT Target
0 to 2
---
1
F109
0 (Self-reset)
"
A07E
POTT Events
0 to 1
---
1
F102
0 (Disabled)
VT Fuse Failure Settings (Read/Write) (2, 4, or 6 Modules)
C60, C70, D30,
D60, F60, G30,
G60, L30, L60,
L90, M60, N60,
T60
A09A
VT Fuse Failure Function
0 to 1
---
1
F102
0 (Disabled)
"
A09B
VT Fuse Failure Neutral Wire Open Function 0 to 1
---
1
F102
0 (Disabled)
"
A09C
VT Fuse Failure Neutral Wire Open 3rd
Harmonic Pickup
0 to 3
pu
0.001 F001
100
"
A09D
VT Fuse Failure 1 Alarm Delay
0 to 65.535
s
0.001 F001
1000
"
A09E
...Repeated for Source 2
C60, C70, D60,
F60, G30, G60,
L60, L90, M60,
N60, T60
A0A2
...Repeated for Source 3
"
A0A6
...Repeated for Source 4
C70, N60, T60
A0AA
...Repeated for Source 5
"
A0AE
...Repeated for Source 6
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...