VT Fuse Failure Actuals (Read Only) (2, 4, or 6 Modules)
C60, C70, D30,
D60, F60, G30,
G60, L30, L60,
L90, M60, N60,
T60
A0B2
VTFF x V0 3rd harmonic
0 to 999999.999
V
0.001 F060
0
"
A0B4
...Repeated for Source 2
C60, C70, D60,
F60, G30, G60,
L60, L90, M60,
N60, T60
A0B6
...Repeated for Source 3
"
A0B8
...Repeated for Source 4
C70, N60, T60
A0BA
...Repeated for Source 5
"
A0BC
...Repeated for Source 6
Summator Settings (Read/Write Setting) (6 Modules)
N60
A0C0
Summator 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
A0C1
Summator 1 Input Mode
0 to 1
---
1
F515
0 (SIGNED)
"
A0C2
Summator 1 Hold
0 to 4294967295
---
1
F300
0
"
A0C4
Summator 1 Pickup
–2000000 to
2000000
---
0.001 F004
1000000
"
A0C6
Summator 1 Hysteresis
0.1 to 50
%
0.1
F001
30
"
A0C7
Summator 1 Input (6 items)
0 to 65535
---
1
F600
0
"
A0CD
Summator 1 Scale Factor (6 items)
–2000 to 2000
---
0.000
001
F004
1000000
"
A0D9
Summator 1 Position Selector (6 items)
0 to 4294967295
---
1
F300
0
"
A0E5
Summator 1 Units
---
---
---
F207
(none)
"
A0E7
Summator 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
A0E8
Summator 1 Per-Unit Base
1 to 2000000
---
1
F004
1
"
A0EA
...Repeated for Summator 2
"
A114
...Repeated for Summator 3
"
A13E
...Repeated for Summator 4
"
A168
...Repeated for Summator 5
"
A192
...Repeated for Summator 6
Current Unbalance Actual Values (Read Only)
M60
A200
Current Unbalance
0 to 100
%
0.1
F001
0
Selector Switch Actual Values (Read Only)
All except B90
A210
Selector Switch 1 Position
1 to 7
---
1
F001
0
"
A211
Selector Switch 2 Position
1 to 7
---
1
F001
1
Selector Switch Settings (Read/Write) (2 Modules)
All except B90
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
A281
Selector 1 Range
1 to 7
---
1
F001
7
"
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
"
A283
Selector 1 Step Up
0 to 4294967295
---
1
F300
0
"
A285
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
"
A286
Selector 1 Acknowledge
0 to 4294967295
---
1
F300
0
"
A288
Selector 1 Bit0
0 to 4294967295
---
1
F300
0
"
A28A
Selector 1 Bit1
0 to 4294967295
---
1
F300
0
"
A28C
Selector 1 Bit2
0 to 4294967295
---
1
F300
0
"
A28E
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
"
A28F
Selector 1 Bit Acknowledge
0 to 4294967295
---
1
F300
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...