CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-135
2
"
A90D
Frequency Rate of Change 1 OV
Supervision
0.1 to 3
pu
0.001 F001
700
"
A90E
Frequency Rate of Change 1 Reserved (3
items)
0 to 1
---
1
F001
0
"
A911
...Repeated for Frequency Rate of Change 2
"
A922
...Repeated for Frequency Rate of Change 3
"
A933
...Repeated for Frequency Rate of Change 4
Restricted Ground Fault (Read/Write Grouped Setting) (4 or 6 Modules)
F60, G30, G60,
L90, T60
A960
Restricted Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
A961
Restricted Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
"
A962
Restricted Ground Fault 1 Pickup
0.005 to 30
pu
0.001 F001
80
"
A963
Restricted Ground Fault 1 Slope
0 to 100
%
1
F001
40
"
A964
Restricted Ground Fault 1 Delay
0 to 600
s
0.01
F001
0
"
A965
Restricted Ground Fault 1 Reset Delay
0 to 600
s
0.01
F001
0
"
A966
Restricted Ground Fault 1 Block
0 to 4294967295
---
1
F300
0
"
A968
Restricted Ground Fault 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
A969
Restricted Ground Fault 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
A96A
...Repeated for Restricted Ground Fault 2
"
A974
...Repeated for Restricted Ground Fault 3
"
A97E
...Repeated for Restricted Ground Fault 4
F60, G60, L90,
T60
A988
...Repeated for Restricted Ground Fault 5
"
A992
...Repeated for Restricted Ground Fault 6
IEC 61850 Received Analog Settings (Read/Write) (32 Modules)
All
AA00
IEC 61850 GOOSE Analog 1 Default Value
–1000000 to
1000000
---
0.001 F060
1000
"
AA02
IEC 61850 GOOSE Analog Input 1 Mode
0 to 1
---
1
F491
0 (Default
Value)
"
AA03
IEC 61850 GOOSE Analog Input 1 Units
---
---
---
F207
(none)
"
AA05
IEC 61850 GOOSE Analog Input 1 Per-Unit
Base
0 to 999999999.999 ---
0.001 F060
1
"
AA07
...Repeated for IEC 61850 GOOSE Analog
Input 2
"
AA0E
...Repeated for IEC 61850 GOOSE Analog
Input 3
"
AA15
...Repeated for IEC 61850 GOOSE Analog
Input 4
"
AA1C
...Repeated for IEC 61850 GOOSE Analog
Input 5
"
AA23
...Repeated for IEC 61850 GOOSE Analog
Input 6
"
AA2A
...Repeated for IEC 61850 GOOSE Analog
Input 7
"
AA31
...Repeated for IEC 61850 GOOSE Analog
Input 8
"
AA38
...Repeated for IEC 61850 GOOSE Analog
Input 9
"
AA3F
...Repeated for IEC 61850 GOOSE Analog
Input 10
"
AA46
...Repeated for IEC 61850 GOOSE Analog
Input 11
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...