CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-193
2
F560
ENUMERATION: IN-ZONE TRANSFORMER CONNECTION
F561
ENUMERATION: 87L INRUSH INHIBIT MODE
F562
ENUMERATION: 87L IN-ZONE TRANSFORMER LOCATION
F563
ENUMERATION: DSCP TYPE
F600
UR_UINT16: FLEXANALOG PARAMETER
Corresponds to the Modbus address of the value used when this
parameter is selected. Only certain values can be used as FlexAn-
alogs (basically all metering quantities used in protection).
F601
ENUMERATION: COM2 PORT USAGE
F602
ENUMERATION: RRTD BAUD RATE
F603
ENUMERATION: RRTD TRIP VOTING
F605
ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
STATUS
Enumeration In-zone transformer connection
0
None
1
0° lag
2
30° lag
3
60° lag
4
90° lag
5
120° lag
6
150° lag
7
180° lag
8
210° lag
9
240° lag
10
270° lag
11
300° lag
12
330° lag
Enumeration Inrush inhibit mode
0
Disabled
1
Per phase
2
Two out of three
3
Average
Enumeration In-zone transformer location
0
Local-Tap
1
Remote 1-Tap
2
Remote 2-Tap
Enumeration DSCP type
0
None
1
Expedited Forwarding
Enumeration COM2 port usage
0
RS485
1
RRTD
2
GPM-F
3
RRTD & GPM-F
Enumeration RRTD baud rate
0
1200 bps
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
Enumeration RRTD trip voting
0
None
1
Group
2
Remote RTD 1
3
Remote RTD 2
4
Remote RTD 3
5
Remote RTD 4
6
Remote RTD 5
7
Remote RTD 6
8
Remote RTD 7
9
Remote RTD 8
10
Remote RTD 9
11
Remote RTD 10
12
Remote RTD 11
13
Remote RTD 12
Enumeration Remote DPS input status
0
intermediate-state
1
off
2
on
3
bad-stqte
4
Latest
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...