3-20
UR SERIES – COMMUNICATIONS GUIDE
PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
UR devices and EnerVista UR Setup automatically detect whether an imported CID file uses the G3 or the E3-2.0 model. UR
devices do not generate CID files, they only make available a copy of the most recently received and accepted CID file. The
model used when EnerVista UR Setup generates a CID file is determined by the Configuration Type setting.
ICD files generated by UR devices and EnerVista UR Setup have factory default settings that do not have GOOSE
subscription configured, and so implement both the G2 and the E3-2.0 model. IID files generated by UR devices and
EnerVista UR Setup are constrained by the standard to have only one IED element, and so for IID files the G2 model and the
E3-2.0 model are equivalent, provided the E3-2.0 extensions are populated, which they are. Thus only CID files generated
by EnerVista UR Setup are sensitive to the Configuration Type setting.
3.3 Protocol implementation conformance statement (PICS)
3.3.1 Basic conformance statement
The tables contain the basic conformance statement.
Table 3-2: PICS for A-profile support
Table 3-3: PICS for T-profile support
3.4 ACSI conformance statement
3.4.1 ACSI basic conformance statement
The table contains the Abstract Communication Service Interface (ACSI) conformance statement.
Table 3-4: ACSI basic conformance statement
Profile description
Client / subscriber
Server / publisher
Value / comments
A1
Client/Server A-Profile per IEC 61850 8 1 clause 6.2.2
Yes
A2
GOOSE/GSE management A-Profile per IEC 61850 8 1
clause 6.3.2
Yes
A3
GOOSE A-Profile per IEC 61850 8 1 clause 6.3.2
Yes
Yes
A4
TimeSync A-Profile
Yes
A5
Security for Client/server A-Profile
A6
Security for GOOSE/GSE management A-Profile
A7
SV A-Profile per IEC 61850 9 2 clause 5.3.2
Profile description
Client / subscriber
Server / publisher
Value / comments
T1
TCP/IP T-Profile per IEC 61850 8 1 clause 6.2.2
Yes
RJ-45 and/or LC
T2
SV T-Profile per IEC 61850 9 2 clause 5.3.3
T3
GOOSE T-Profile per IEC 61850 8 1 clause 6.3.3
Yes
Yes
RJ-45 and/or LC
T4
GSSE T-Profile
deprecated
T5
TimeSync T-Profile per IEC 61850 8 1 clause 6.4.3
Yes
RJ-45 and/or LC
Client / subscriber Server / publisher Value / comments
Client-server roles
B11
Server side (of Two-party Application-Association)
Yes
B12
Client side (of Two-party Application-Association)
SCSMs supported
B21
SCSM: IEC 61850-8-1 used
Yes
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...