CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-33
3
3.5.1.4 GOOSE subscription monitor (LGOS)
LGOS is instantiated in all UR series devices.
See the
G2 implementation model for GOOSE configuration via SCL
section on page 3-162 for descriptions of data objects
MAC, APPID, GoDatSetRef, GoID, ConfRev and InRef
δδ
.
Table 3-13: GOOSE subscription monitor data objects
stVal
BOOLEAN
ST RTD TROUBLE
R
TdrTrbl
SPS
TDR TROUBLE operand
R
stVal
BOOLEAN
ST TDR TROUBLE
R
InRef1
ORG
PROCESS BUS FAILURE setting
R
setSrcRef
ObjectReference
SP PROCESS BUS FAILURE setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
LGOS#
LDevice inst:
Prot
UR element:
Mapped to setting RxGOOSE# ID if not empty string, otherwise
“RxGOOSE#
data obj. data attribute
Type
FC UR Name
Description
R/W/C
St
SPS
RxGOOSE# On operand
R
stVal
BOOLEAN
ST RxGOOSE# On
R
Alm
SPS
RxGOOSE# Off operand
R
stVal
BOOLEAN
ST RxGOOSE# Off
R
SimSt
SPS
Status showing that Sim messages are
being received and accepted for RxGOOSE#
R
stVal
BOOLEAN
ST Status showing that really Sim
messages are received and
accepted
R
LastStNum
INS
Actual value RxGOOSE# stNum
R
stVal
INT32
ST Actual value RxGOOSE# stNum
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1
R
units.multiplier
ENUMERATED
0
R
LastSqNum
INS
Actual value RxGOOSE# sqNum
R
stVal
INT32
ST Actual value RxGOOSE# sqNum
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1
R
units.multiplier
ENUMERATED
0
R
ConfRevNu
m
INS
Status of the confRev field in last accepted
RxGOOSE# message
R
stVal
INT32
ST Status of the confRev field in last
accepted RxGOOSE# message
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1
R
units.multiplier
ENUMERATED
0
R
GoCBRef
ORG
R
setSrcRef
ObjectReference
SP Mapped to RxGOOSE# GoCBRef
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R
MAC
VSG
Destination MAC address of messages
subscribed to by RxGOOSE#
R
setVal
VISIBLE
STRING255
SP RxGOOSE# Dst MAC
R/C
APPID
ING
Setting RxGOOSE# ETYPE APPID
R
setVal
INT32
SP RxGOOSE# ETYPE APPID
R/C
minVal
INT32
CF
0
R
LNName:
LPHD1
LDevice inst:
Master
UR element:
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...