3-36
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.1.8 FlexAnalog operand interface (GGIO4)
GGIO4 is instantiated in all UR series devices.
Table 3-17: FlexAnalog data objects
LNName:
<configured GGIO4
prefix>GGIO4
LDevice inst:
Master
UR element:
FlexAnalog Operand Interface functionality
data obj. data attribute
Type
FC UR Name
Description
R/W/C
AnIn
ψψ
MV
The name of the operand selected by
setting ANALOG IN
ψ
VALUE
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
The operand selected by setting
ANALOG IN
ψ
VALUE
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
The operand selected by setting ANALOG IN
ψ
VALUE, deadbanded
R
db
INT32U
CF ANALOG IN
ψ
DB
R/W/C
zeroDb
INT32U
CF
0
R
DbMax
ψψ
ASG
This logical node’s behavior
R
setMag
AnalogueValue
SP
R
setMag.f
FLOAT32
ANALOG IN
ψ
MAX
R/C
minVal
AnalogueValue
CF
R
minVal.f
FLOAT32
-1 000 000 000
R
maxVal
AnalogueValue
CF
R
maxVal.f
FLOAT32
1 000 000 000
R
stepSize
AnalogueValue
CF
R
stepSize.f
FLOAT32
0.001
R
DbMin
ψψ
ASG
This logical node’s behavior
R
setMag
AnalogueValue
SP
R
setMag.f
FLOAT32
ANALOG IN
ψ
MIN
R/C
minVal
AnalogueValue
CF
R
minVal.f
FLOAT32
-1 000 000 000
R
maxVal
AnalogueValue
CF
R
maxVal.f
FLOAT32
1 000 000 000
R
stepSize
AnalogueValue
CF
R
stepSize.f
FLOAT32
0.001
R
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...