CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-41
3
3.5.2.6 B90 end fault protection (B_Efp)
This element is instantiated in the following products: B90.
Table 3-24: B90 end fault protection data objects
3.5.2.7 B90 instantaneous overcurrent (B_Ioc)
This element is instantiated in the following products: B90.
Table 3-25: B90 instantaneous overcurrent data objects
3.5.2.8 B90 time overcurrent (B_Toc)
This element is instantiated in the following products: B90.
setSrcRef
ObjectReference
SP BUS ZONE #
τ
STATUS setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
B_EfpPIOC#
LDevice inst:
Prot
UR element:
B90 End fault protection element # function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
EFP # PKP operand
R
general
BOOLEAN
ST EFP # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional
R
Op
ACT
EFP # OP operand
R
general
BOOLEAN
ST EFP # OP
R
Dpo
SPS
EFP # DPO operand, which is the inverse of
EFP PKP
R
stVal
BOOLEAN
ST EFP # DPO
R
InRef
γ
1
ORG
EFP# BREAKER OPEN setting for setting
group
γ
R
setSrcRef
ObjectReference
SP EFP# BREAKER OPEN for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
2
ORG
EFP# MANUAL CLOSE setting for setting
group
γ
R
setSrcRef
ObjectReference
SP EFP# MANUAL CLOSE for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef
γ
ORG
EFP# BLOCK setting for setting group
γ
R
setSrcRef
ObjectReference
SP EFP# BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
B_IocPIOC#
LDevice inst:
Prot
UR element:
B90 Instantaneous Overcurrent element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
IOC # PKP operand, which indicates that Op
operates when delay expires
R
general
BOOLEAN
ST IOC # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
IOC # OP operand
R
general
BOOLEAN
ST IOC # OP
R
Dpo
SPS
IOC # DPO operand
R
stVal
BOOLEAN
ST IOC # DPO
R
BlkRef
γ
ORG
IOC# BLOCK setting for setting group
γ
R
setSrcRef
ObjectReference
SP IOC# BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
B_DifPDIF#
LDevice inst:
Prot
UR element:
B90 Bus zone # differential element function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...