3-42
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-26: B90 time overcurrent data objects
3.5.2.9 B90 undervoltage (B_Uv)
This element is instantiated in the following products: B90.
Table 3-27: B90 undervoltage data objects
3.5.2.10 Breaker failure (BkrFa)
This element is instantiated in the following products: B30, C60, C70, D60, F60, G60, L30, L60, L90, M60, T60.
Table 3-28: Breaker failure data objects
LNName:
B_TocPTOC#
LDevice inst:
Prot
UR element:
Time Overcurrent element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
TOC# PKP operand, which indicates that Op
operates when delay expires
R
general
BOOLEAN
ST TOC# PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
TOC# OP operands (including individual
three phases)
R
general
BOOLEAN
ST TOC# OP
R
Dpo
SPS
TOC# DPO operand
R
stVal
BOOLEAN
ST TOC# DPO
R
DpoPhs1
SPS
TOC# DPO operand
R
stVal
BOOLEAN
ST TOC# DPO
R
BlkRef
γ
ORG
TOC# BLOCK setting for setting group
γ
R
setSrcRef
ObjectReference
SP TOC# BLOCK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
B_UvPTUV#
LDevice inst:
Prot
UR element:
B90 Undervoltage element # function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
UNDERVOLTAGE # PKP operands
R
general
BOOLEAN
ST UNDERVOLTAGE # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown. It is unknown as
the element is non-directional.
R
Op
ACT
UNDERVOLTAGE # OP operand
R
general
BOOLEAN
ST UNDERVOLTAGE # OP
R
Dpo
SPS
UNDERVOLTAGE # DPO operand, which is
the inverse of UNDERVOLTAGE PKP
R
stVal
BOOLEAN
ST UNDERVOLTAGE # DPO
R
BlkRef
γ
ORG
UNDERVOLTAGE # BLK setting for setting
group
γ
R
setSrcRef
ObjectReference
SP UNDERVOLTAGE # BLK for group
γ
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
BkrFaRBRF#
LDevice inst:
Prot
UR element:
Breaker Control element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
InRef
γ
02
ORG
BF# 3-POLE INITIATE setting for setting
group
γ
R
setSrcRef
ObjectReference
SP 3-POLE INITIATE input
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef
γ
ORG
BF# BLOCK setting for setting group
γ
R
setSrcRef
ObjectReference
SP BF# BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef
γ
03
ORG
BF# BKR POS1
φ
A/3P setting for setting
group
γ
R
setSrcRef
ObjectReference
SP BF# BKR POS1
φ
A/3P
Reference to the data attribute to input
R/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...