3-52
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.21 Hybrid permissive over-reaching transfer trip (HPOTT_)
This element is instantiated in the following products: D60, L90.
Table 3-40: Hybrid POTT data objects
3.5.2.22 Line current differential (LinDif)
This element is instantiated in the following products: L30, L90.
LNName:
HPOTT_PSCH1
LDevice inst:
Prot
UR element:
Hybrid Permissive Over-reaching Transfer Trip element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
HYBRID POTT OP operand
R
general
BOOLEAN
ST HYBRID POTT OP
R
phsA
BOOLEAN
ST HYBRID POTT TRIP A
R
phsB
BOOLEAN
ST HYBRID POTT TRIP B
R
phsC
BOOLEAN
ST HYBRID POTT TRIP C
R
Tr3p
ACT
HYBRID POTT TRIP 3P operand
R
general
BOOLEAN
ST HYBRID POTT TRIP 3P
R
Tx1
SPS
HYBRID POTT TX1 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX1
R
Tx2
SPS
HYBRID POTT TX2 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX2
R
Tx3
SPS
HYBRID POTT TX3 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX3
R
Tx4
SPS
HYBRID POTT TX4 operand
R
stVal
BOOLEAN
ST HYBRID POTT TX4
R
BlkRef1
ORG
HYB POTT SCHEME BLOCK setting
R
setSrcRef
ObjectReference
SP HYB POTT SCHEME BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef5
ORG
HYB POTT ECHO COND setting
R
setSrcRef
ObjectReference
SP HYB POTT ECHO COND
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef8
ORG
HYB POTT W/I COND setting
R
setSrcRef
ObjectReference
SP HYB POTT W/I COND
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef6
ORG
GND DIR O/C FWD setting
R
setSrcRef
ObjectReference
SP GND DIR O/C FWD
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef7
ORG
GND DIR O/C REV setting
R
setSrcRef
ObjectReference
SP GND DIR O/C REV
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef1
ORG
HYB POTT RX1 setting
R
setSrcRef
ObjectReference
SP HYB POTT RX1
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
ORG
HYB POTT RX2 setting
R
setSrcRef
ObjectReference
SP HYB POTT RX2
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef3
ORG
HYB POTT RX3 setting
R
setSrcRef
ObjectReference
SP HYB POTT RX3
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef4
ORG
HYB POTT RX4 setting.
R
setSrcRef
ObjectReference
SP HYB POTT RX4
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...