CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-73
3
dirPhsB
ENUMERATED
ST
0
R
phsC
BOOLEAN
ST XFMR PCNT DIFF PKP C
R
dirPhsC
ENUMERATED
ST
0
R
RefWinding
INS
Number of winding used as the reference
winding for ratio compensation
R
stVal
INT32
ST REFERENCE WINDING
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
1, the code for dimensionless
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
DifAClc
WYE
Phase differential currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
DIFF PHASOR I
θ
d magnitude, in
primary amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
DIFF PHASOR
UR range -180...+180 converted to 0...360
R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
DIFF PHASOR I
θ
d magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
DIFF PHASOR
UR range -180...+180 converted to 0...360
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit
ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF PctDifPDIF1.DifAClc.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
DifA2ndH
WYE
Phase differential currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
DIFF 2ND HARM I
θ
d magnitude, in
primary amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
DIFF 2ND HA
UR range -180...+180 converted to 0...360
R
phs
θ
.cVal
Vector
MX
R
phs
θ
.cVal.mag.f
FLOAT32
DIFF 2ND HARM I
θ
d magnitude, in
primary amps, with deadband
R
phs
θ
.cVal.ang.f
FLOAT32
DIFF 2ND HA
UR range -180...+180 converted to 0...360
R
phs
θ
.units
Unit
CF
R
phs
θ
.units.SIUnit
ENUMERATED
5, the code for amps
R
phs
θ
.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
phs
θ
.db
INT32U
CF PctDifPDIF1.DifA2ndH.phs
θ
.db
R/W/C
phs
θ
.zeroDb
INT32U
CF
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
DifA5thH
WYE
Phase differential currents
R
phs
θ
CMV
R
phs
θ
.instCVal
Vector
MX
R
phs
θ
.instCVal.mag
.f
FLOAT32
DIFF 5TH HARM I
θ
d magnitude, in
primary amps
R
phs
θ
.instCVal.ang
.f
FLOAT32
DIFF 5TH HA
UR range -180...+180 converted to 0...360
R
LNName:
PctDifPDIF1
LDevice inst:
Prot
UR element:
Transformer Percent Differential function
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...