CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-75
3
3.5.2.49 Trip output (TrOut)
This element is instantiated in the following products: D60, L60, L90.
Table 3-72: Trip output data objects
InRef99
ORG
TRIP BUS # RESET setting, which when On
resets the non-volatile set-dominant input
conditions latch
R
setSrcRef
ObjectReference
SP TRIP BUS # RESET setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
BlkRef1
ORG
TRIP BUS # BLOCK setting
R
setSrcRef
ObjectReference
SP TRIP BUS # BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
TrOutPTRC1
LDevice inst:
Prot
UR element:
Trip Output element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Tr
ACT
TRIP OUTPUT OP (any trip) operand
R
general
BOOLEAN
ST TRIP OUTPUT OP
R
Tr3p
ACT
TRIP 3-POLE operand
R
general
BOOLEAN
ST TRIP 3-POLE
R
Tr1p
ACT
General is TRIP 1-POLE operand, phsA is
TRIP PHASE A operand, phsB is TRIP PHASE
B operand and phsC is TRIP PHASE C
operand
R
general
BOOLEAN
ST TRIP 1-POLE
R
phsA
BOOLEAN
ST TRIP PHASE A
R
phsB
BOOLEAN
ST TRIP PHASE B
R
phsC
BOOLEAN
ST TRIP PHASE C
R
StrRec3p
SPS
TRIP AR INIT 3-POLE operand
R
stVal
BOOLEAN
ST TRIP AR INIT 3-POLE
R
Tr3pFrcd
SPS
TRIP FORCE 3-POLE operand (3-pole trip
mode is being forced)
R
stVal
BOOLEAN
ST TRIP FORCE 3-POLE
R
StrZ2PhDl
SPS
TRIP Z2PH TMR INIT operand
R
stVal
BOOLEAN
ST TRIP Z2PH TMR INIT
R
StrZ2GndDl
SPS
TRIP Z2GR TMR INIT operand
R
stVal
BOOLEAN
ST TRIP Z2GR TMR INIT
R
InRef3
α
ORG
TRIP 3-POLE INPUT-
α
setting
R
setSrcRef
ObjectReference
SP TRIP 3-POLE INPUT-
α
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef1
α
ORG
TRIP 1-POLE INPUT-
α
setting
R
setSrcRef
ObjectReference
SP TRIP 1-POLE INPUT-
α
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef2
α
ORG
TRIP RECLOSE INPUT-
α
setting
R
setSrcRef
ObjectReference
SP TRIP RECLOSE INPUT-
α
setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef01
ORG
START TMR Z2PH Inp1 setting
R
setSrcRef
ObjectReference
SP START TMR Z2PH Inp1 setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef02
ORG
START TMR Z2PH Inp2 setting
R
setSrcRef
ObjectReference
SP START TMR Z2PH Inp2 setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
TrBusPTRC#
LDevice inst:
Prot
UR element:
Trip Bus element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...