3-76
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.50 Underfrequency (UnHz)
This element is instantiated in the following products: D60, F35, F60, G30, G60, L30, L90, M60, N60, T60.
Table 3-73: Underfrequency data objects
3.5.2.51 Volts per Hertz (VpHz)
This element is instantiated in the following products: G30, G60, T60.
Table 3-74: Volts per Hertz data objects
InRef03
ORG
START TMR Z2GR Inp1 setting
R
setSrcRef
ObjectReference
SP START TMR Z2GR Inp1 setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef04
ORG
START TMR Z2GR Inp2 setting
R
setSrcRef
ObjectReference
SP START TMR Z2GR Inp2 setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef05
ORG
BKR
φ
A OPEN setting
R
setSrcRef
ObjectReference
SP BKR
φ
A OPEN setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef06
ORG
BKR
φ
B OPEN setting
R
setSrcRef
ObjectReference
SP BKR
φ
B OPEN setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef07
ORG
BKR
φ
C OPEN setting
R
setSrcRef
ObjectReference
SP BKR
φ
C OPEN setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef08
ORG
TRIP FORCE 3-POLE setting
R
setSrcRef
ObjectReference
SP TRIP FORCE 3-POLE setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
InRef09
ORG
REVERSE FAULT setting
R
setSrcRef
ObjectReference
SP REVERSE FAULT setting
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
UnHzPTUF#
LDevice inst:
Prot
UR element:
Underfrequency element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Str
ACD
UNDERFREQ # PKP operand, which
indicates that Op operates when delay
expires
R
general
BOOLEAN
ST UNDERFREQ # PKP
R
dirGeneral
ENUMERATED
ST
0, the code for unknown
R
Op
ACT
UNDERFREQ # OP operand
R
general
BOOLEAN
ST UNDERFREQ # OP
R
Dpo
SPS
UNDERFREQ # DPO operand
R
stVal
BOOLEAN
ST UNDERFREQ # DPO
R
BlkRef1
ORG
UNDERFREQ # BLOCK setting
R
setSrcRef
ObjectReference
SP UNDERFREQ # BLOCK
Reference to the data attribute to input
R/C
setSrcCB
ObjectReference
SP
Source GoCB of input if via GOOSE
R/C
LNName:
VpHzPVPH#
LDevice inst:
Prot
UR element:
Volts per Hertz element #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Op
ACT
VOLTS PER HERTZ # OP operand
R
general
BOOLEAN
ST VOLTS PER HERTZ # OP
R
Dpo
SPS
VOLTS PER HERTZ # DPO operand
R
LNName:
TrOutPTRC1
LDevice inst:
Prot
UR element:
Trip Output element
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...