3-114
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-103: AC signal sources data objects
instCVal.ang.i
INT32
SRC # Ground Current Angle
UR range -180...+180 converted to 0...360
R
cVal
Vector
MX
R
cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
cVal.ang.i
INT32
instCVal.ang.i deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for primary amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF MMXN# GndCur DEADBAND
R/W/C
zeroDb
INT32U
CF
Current cut-off level
R
angSVC
ScaledValue
Config
CF
R
angSVC
.scaleFactor
FLOAT32
1/10
R
angSVC.offset
FLOAT32
0
R
angRef
ENUMERATED
CF
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
AgndRMS
MV
SRC # Ground Current RMS, in primary
amperes
R
instMag
AnalogueValue
MX
R
instMag.f
FLOAT32
SRC # Ground Current RMS
R
mag
AnalogueValue
MX
R
mag.f
FLOAT32
instMag.f deadbanded
R
units
Unit
CF
R
units.SIUnit
ENUMERATED
5, the code for primary amperes
R
units.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
db
INT32U
CF MMXN# RMS GndCur DEADBAND
R/W/C
zeroDb
INT32U
CF
Current cut-off level
R
LNName:
ACsrcMSQI#
LDevice inst:
Meter
UR element:
AC Source #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
SeqA
SEQ
SRC # Sequence Current phasors, in
primary amperes
R
c1
CMV
R
c1.instCVal
Vector
MX
R
c1.instCVal.mag.f
FLOAT32
SRC # Positive Sequence Current
Magnitude
R
c1.instCVal.ang.f
FLOAT32
SRC # Positive Sequence Current
Angle
UR range -180...+180 converted to 0...360
R
c1.cVal
Vector
MX
R
c1.cVal.mag.f
FLOAT32
instCVal.mag.f deadbanded
R
c1.cVal.ang.f
FLOAT32
instCVal.ang.i deadbanded
R
c1.units
Unit
CF
R
c1.units.SIUnit
ENUMERATED
5, the code for primary amperes
R
c1.units
.multiplier
ENUMERATED
0, the code for a multiplier of 1
R
c1.db
INT32U
CF MSQI# Seq1 Cur DEADBAND
R/W/C
c1.zeroDb
INT32U
CF
Current cut-off level
R
c2
CMV
R
c2.instCVal
Vector
MX
R
c2.instCVal.mag.f
FLOAT32
SRC # Negative Sequence Current
Magnitude
R
LNName:
ACsrcMMXN#
LDevice inst:
Meter
UR element:
AC Source #
data obj. data attribute
Type
FC UR Name
Description
R/W/C
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...