CHAPTER 3: IEC 61850 COMMUNICATION
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR SERIES – COMMUNICATIONS GUIDE
3-129
3
ArBlk1
SPS
Autoreclose Breaker number indicated by the data instance number is temporarily
disabled
Rec3pRREC,
Rec13pRREC
AresRMS
MV
Residual Current RMS
ACsrcMMXU
ArLO
SPS
Autoreclose is locked out
Rec3pRREC,
Rec13pRREC
ArMod1
SPS
Autoreclosec mode equals to the number indicated by the data instance number, in this
case 1 and 3 pole mode
Rec13pRREC
ArRip
SPS
Autoreclose is in progress
Rec3pRREC,
Rec13pRREC
ASupn
SPS
Indicates the state of current supervision
PhsDisPDIS
Asymmetry
SPS
Communications channel asymmetry detected
LinDfPDIF
BadSt1
SPS
Bad-status detected
Bkr?XCBR,
Disc0XSWI,
Disc?XSWI, GGIO3
BatFail
SPS
The battery is not functioning
LPHD
BDifAClc
CMV
B90 differential current
B_DifPDIF
BkrBlkdMod1
ENG
Action to take when process is blocked: 0 = stop, 1 = use-alternate
Rec13pRREC
BkrOp1
SPS
Breaker failure status information operands
BkrFaRBRF,
B_BFaiRBRF
BkrSeq
ENG
Breaker sequence setting: 0 = reclose-breaker-1-only, 1 = reclose-breaker-2-only, 2 =
reclose-both breakers-simultaneously, 3 = reclose-breaker-1-then-2 – 2, 4 = reclose-
breaker-2–then-1
Rec13pRREC
BkrSeqTmcs
ING
Time between closing the lead breaker and the second breaker
Rec13pRREC
Blk2ndH1
SPS
Indicates second harmonic blocking active (where the last digit of instance number 1, 2,
or 3 refers to phase A, B, and C respectively)
PctDifPDIF1
Blk5thH1
SPS
Indicates fifth harmonic blocking active (where the last digit of instance number 1, 2, or
3 refers to phase A, B, and C respectively)
PctDifPDIF1
BlkH1
SPS
The second harmonic of the transformer magnetizing inrush current has inhibited the
current differential element from operating
LinDfPDIF (L90)
BlkMod1
ENG
Action to take when breaker is blocked: 0 = stop, 1 = use-alternate
Rec13pRREC
BlkTmcs
ING
Duration reclose is blocked after an associated circuit breaker is manually commanded
to close
Rec13pRREC
BrckTrbl
SPS
Brick trouble
LPHD
BRstA
CMV
B90 restraint current
B_DifPDIF
ChA
CMV
B90’s AC channel current
B_AmpMMXN
ChFail1
SPS
Communications channel failed
LinDfPDIF
ChV
CMV
B90’s AC channel voltage
B_VolMMXN
ClkUnsynch
SPS
Relay is not synchronized to the international time standard
LPHD
Cls2ndBkr
SPS
Close second Breaker signal
Rec13pRREC
ClsBkrTmcs1
ING
Closing time of breaker in centiseconds
Rec13pRREC
ClsFailMod1
ENG
Action to take when process fails to respond to a close signal: 0 = use-alternate, 1 =
stop
Rec13pRREC
ClsPlsTmms
ING
Close pulse duration in milliseconds
Bkr?XCBR
ClsSt1
SPS
Close status detected
Bkr?XCBR,
Disc0XSWI,
Disc?XSWI, GGIO3
ConfRev
ING
Expected value of confRev field in messages subscribed to by RxGOOSE#
LGOS
Connection
ENG
Auxiliary AC input connection: 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca ACinTVTR
CrcFail1
SPS
The CRC error threshold has been exceeded
LinDfPDIF
DbMax1
ASG
Value of “max.” in deadband calculations
GGIO4
DbMin1
ASG
Value of “min.” in deadband calculations
GGIO4
Data object
name
CDC
Semantics
Used in logical
nodes…
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...