ProcBusFail
SPS
Process bus system status
LPHD
ProcBusTrbl
SPS
Process Bus Trouble
LPHD
PtpFail
SPS
Bad PTP Signal
LPHD
RecMod
ENG
AR Mode setting: 1 = 1 and 3 Pole, 2 = 1 Pole, 3 = 3 Pole-A, 4 = 3 Pole-B
Rec13pRREC
RefWinding
INS
Reference winding
PctDifPDIF1
RelDpo
SPS
This data object indicates that not all criteria are fulfilled, and the switching/operation
action is not released to proceed. Complement of Rel.
SynChkRSYN
RrtdComFail
SPS
RRTD communication failure
LPHD
Rs
SPS
Autoreclose has been reset either manually or by the rest timer
Rec13pRREC
RsLO1
ENG
Reset lockout on condition setting: 0 = Off, 1 = On, in this case on Breaker Closed
condition
Rec3pRREC
RsLOTmcs
ING
This setting establishes how long the breaker stays closed after a manual close
command, in order for the autorecloser to reset from lockout
Rec3pRREC
RsTms
INS
The UTC time of the last clear in seconds elapsed since 00:00:00 January 1, 1970
OscRDRE
RtdTrbl
SPS
RTD Trouble
LPHD
RvOp
SPS
Fault direction is reverse
NegDocRDIR,
NeuDocRDIR
RxGooseOff
SPS
One or more RxGOOSE is not responding
LPHD
Sat1
SPS
Indicates CT saturation is detected.
For SttDifPDIF, indicates phase saturation of differential is detected per phase.
B_DifPDIF, SttDifPDIF
Sat
1
SPS
Indicates CT saturation is detected per phase (where the last digit of instance number
1, 2, or 3 refers to phase A, B, and C respectively)
BusDifPDIF
SecEthFail
SPS
Second Ethernet failure
LPHD
SeqDlTmcs
ING
Time interval allowed for a single reclose shot. Timing is started whenever reclose shot
is initiated and is active until a breaker closed signal is sent.
Rec3pRREC,
Rec13pRREC
SeqTO
SPS
The incomplete sequence timer timed out
Rec13pRREC
ShotCnt1
SPS
Autoreclosec # shot count is equal to the number indicated by the data instance
number
Rec3pRREC
ShotCnt1
SPS
Autoreclosec shot count is equal to the number indicated by the data instance number Rec13pRREC
SntpFail
SPS
SNTP server is not responding
LPHD
StrBia
ACD
B90 Start Biased indicates the detection of a fault or an unacceptable condition by
Biased Differential element
B_DifPDIF
StrOutgoing
SPS
This Data Object indicates an unstable Power swing detection for outgoing Locus
PwrSwgRPSB1
StrPhs
SPS
Indicates the detection of a fault or an unacceptable condition on a particular phase-
to-phase loop
PhsDisPDIS
StrRec3p
SPS
Initiate a three-pole reclose
TrOutPTRC
StrZ2GndDl
SPS
Start zone 2 ground timer
TrOutPTRC
StrZ2PhDl
SPS
Start zone 2 phase timer
TrOutPTRC
StTyp
ENG
Switch input status type: 0 = 3-Pole (i.e. not independent pole status), 1 = 1-Pole (i.e.
three independent pole status)
Bkr?XCBR,
StubBusOp
SPS
The stub bus function is operated
LinDfPDIF
SwFail
SPS
Autoreclose mode switching failed
Rec13pRREC
SysExcp
SPS
System exception
LPHD
TdrTrbl
SPS
TDR Trouble
LPHD
TempMnt
SPS
The ambient temperature is greater than the maximum operating temperature
LPHD
TgtEna1
ENG
Enable generation of targets (front panel display messages) setting: 0 = Self-reset, 1 =
Latched, and 2 = Disabled
AuxOvPTOV,
AuxUvPTUV,
B_IocPIOC,
B_TocPTOC,
BkrFaRBRF
ThrdEthFail
SPS
Third Ethernet failure
LPHD
Data object
name
CDC
Semantics
Used in logical
nodes…
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...