CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-31
2
"
2331
Transformer Hottest Spot Temperature
0 to 300
°C
1
F002
0
"
2332
Transformer Aging Factor
0 to 6553.5
PU
0.1
F001
0
"
2333
Transformer Daily Loss of Life
0 to 500000
Hours
1
F060
0
Transformer Thermal Inputs Actual Values (Read Only Non-Volatile)
T60
2335
Transformer Loss of Life
0 to 500000
Hours
1
F060
0
Fault Location (Read Only) (5 Modules)
C60, D30, D60,
F35, F60, L30,
L60, L90
2340
Fault 1 Prefault Phase A Current Magnitude 0 to 999999.999
A
0.001 F060
0
"
2342
Fault 1 Prefault Phase A Current Angle
-359.9 to 0
degrees 0.1
F002
0
"
2343
Fault 1 Prefault Phase B Current Magnitude 0 to 999999.999
A
0.001 F060
0
"
2345
Fault 1 Prefault Phase B Current Angle
-359.9 to 0
degrees 0.1
F002
0
"
2346
Fault 1 Prefault Phase C Current Magnitude 0 to 999999.999
A
0.001 F060
0
"
2348
Fault 1 Prefault Phase C Current Angle
-359.9 to 0
degrees 0.1
F002
0
"
2349
Fault 1 Prefault Phase A Voltage Magnitude 0 to 999999.999
V
0.001 F060
0
"
234B
Fault 1 Prefault Phase A Voltage Angle
-359.9 to 0
degrees 0.1
F002
0
"
234C
Fault 1 Prefault Phase B Voltage Magnitude 0 to 999999.999
V
0.001 F060
0
"
234E
Fault 1 Prefault Phase B Voltage Angle
-359.9 to 0
degrees 0.1
F002
0
"
234F
Fault 1 Prefault Phase C Voltage Magnitude 0 to 999999.999
V
0.001 F060
0
"
2351
Fault 1 Prefault Phase C Voltage Angle
-359.9 to 0
degrees 0.1
F002
0
"
2352
Fault 1 Phase A Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
2354
Fault 1 Phase A Current Angle
-359.9 to 0
degrees 0.1
F002
0
"
2355
Fault 1 Phase B Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
2357
Fault 1 Phase B Current Angle
-359.9 to 0
degrees 0.1
F002
0
"
2358
Fault 1 Phase C Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
235A
Fault 1 Phase C Current Angle
-359.9 to 0
degrees 0.1
F002
0
"
235B
Fault 1 Phase A Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
235D
Fault 1 Phase A Voltage Angle
-359.9 to 0
degrees 0.1
F002
0
"
235E
Fault 1 Phase B Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
2360
Fault 1 Phase B Voltage Angle
-359.9 to 0
degrees 0.1
F002
0
"
2361
Fault 1 Phase C Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
2363
Fault 1 Phase C Voltage Angle
-359.9 to 0
degrees 0.1
F002
0
"
2364
Fault 1 Type
0 to 11
---
1
F148
0 (NA)
"
2365
Fault 1 Location based on Line length units
(km or miles)
-3276.7 to 3276.7
---
0.1
F002
0
"
2366
...Repeated for Fault 2
"
238C
...Repeated for Fault 3
"
23B2
...Repeated for Fault 4
"
23D8
...Repeated for Fault 5
Synchrocheck Actual Values (Read Only) (4 Modules)
C60, D30, D60,
F60, G30, G60,
L30, L60, L90,
N60, T60
2400
Synchrocheck 1 Delta Voltage
-1000000000000 to
1000000000000
V
1
F060
0
"
2402
Synchrocheck 1 Delta Frequency
0 to 655.35
Hz
0.01
F001
0
"
2403
Synchrocheck 1 Delta Phase
0 to 359.9
degrees 0.1
F001
0
"
2404
...Repeated for Synchrocheck 2
"
2408
...Repeated for Synchrocheck 3
"
240C
...Repeated for Synchrocheck 4
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...