2-34
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
2550
... Repeated for DPS 5
Phasor Measurement Unit Actual Values (Read Only) (1, 2, 4, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
256D
PMU 1 Phase A Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
256F
PMU Unit 1 Phase A Voltage Angle
-180 to 180
°
0.01
F002
0
"
2570
PMU 1 Phase B Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
2572
PMU 1 Phase B Voltage Angle
-180 to 180
°
0.01
F002
0
"
2573
PMU 1 Phase C Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
2575
PMU 1 Phase C Voltage Angle
-180 to 180
°
0.01
F002
0
"
2576
PMU 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
2578
PMU 1 Auxiliary Voltage Angle
-180 to 180
°
0.01
F002
0
"
2579
PMU 1 Positive Sequence Voltage
Magnitude
0 to 999999.999
V
0.001 F060
0
"
257B
PMU 1 Positive Sequence Voltage Angle
-180 to 180
°
0.01
F002
0
"
257C
PMU 1 Negative Sequence Voltage
Magnitude
0 to 999999.999
V
0.001 F060
0
"
257E
PMU 1 Negative Sequence Voltage Angle
-180 to 180
°
0.01
F002
0
"
257F
PMU 1 Zero Sequence Voltage Magnitude
0 to 999999.999
V
0.001 F060
0
"
2581
PMU 1 Zero Sequence Voltage Angle
-180 to 180
°
0.01
F002
0
"
2582
PMU 1 Phase A Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
2584
PMU 1 Phase A Current Angle
-180 to 180
°
0.01
F002
0
"
2585
PMU 1 Phase B Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
2587
PMU 1 Phase B Current Angle
-180 to 180
°
0.01
F002
0
"
2588
PMU 1 Phase C Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
258A
PMU 1 Phase C Current Angle
-180 to 180
°
0.01
F002
0
"
258B
PMU 1 Ground Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
258D
PMU 1 Ground Current Angle
-180 to 180
°
0.01
F002
0
"
258E
PMU 1 Positive Sequence Current
Magnitude
0 to 999999.999
A
0.001 F060
0
"
2590
PMU 1 Positive Sequence Current Angle
-180 to 180
°
0.01
F002
0
"
2591
PMU 1 Negative Sequence Current
Magnitude
0 to 999999.999
A
0.001 F060
0
"
2593
PMU 1 Negative Sequence Current Angle
-180 to 180
°
0.01
F002
0
"
2594
PMU 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001 F060
0
"
2596
PMU 1 Zero Sequence Current Angle
-180 to 180
°
0.01
F002
0
"
2597
PMU 1 Frequency
2 to 90
Hz
0.001 F003
0
"
2599
PMU 1 df/dt
-327.67 to 327.67
Hz/s
0.01
F002
0
"
259A
PMU 1 Configuration Change Counter
0 to 65535
---
1
F001
0
"
259B
Reserved (4 items)
0 to 1
---
1
F001
0
C60, N60
259F
...Repeated for PMU 2
N60
25D1
...Repeated for PMU 3
"
2603
...Repeated for PMU 4
"
2635
...Repeated for PMU 5
"
2667
...Repeated for PMU 6
Phasor Measurement Unit Integer (Read Only) (1, 2, 4, or 6 Modules)
C60, D60, F60,
G60, L30, L90,
N60, T60
2699
PMU 1 SOC Timestamp
0 to 4294967295
seconds 1
F003
0
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...