2-36
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
Expanded FlexStates (Read Only)
All
2B00
FlexStates, one per register (256 items)
0 to 1
---
1
F108
0 (Off)
Expanded Contact Input/Output States (Read Only)
All
2D00
Contact Input States, one per register (96
items)
0 to 1
---
1
F108
0 (Off)
"
2D80
Contact Output States, one per register (64
items)
0 to 1
---
1
F108
0 (Off)
"
2E00
Virtual Output States, one per register (96
items)
0 to 1
---
1
F108
0 (Off)
Expanded Remote Input/Output Status (Read Only)
All
2F00
Remote Device States, one per register (32
items)
0 to 1
---
1
F155
0 (Offline)
"
2F80
RxGOOSE Boolean x States, one per
register (128 items)
0 to 1
---
1
F108
0 (Off)
Oscillography Values (Read Only)
All
3000
Oscillography Number of Triggers
0 to 65535
---
1
F001
0
"
3001
Oscillography Available Records
0 to 65535
---
1
F001
0
"
3002
Oscillography Last Cleared Date
0 to 400000000
---
1
F050
0
"
3004
Oscillography Number Of Cycles Per
Record
0 to 65535
---
1
F001
0
Oscillography Commands (Read/Write Command)
All
3005
Oscillography Force Trigger
0 to 1
---
1
F126
0 (No)
"
3011
Oscillography Clear Data
0 to 1
---
1
F126
0 (No)
Oscillography Analog Values (Read Only)
All
3012
Oscillography Number of Triggers
0 to 32767
---
1
F001
0
Fault Report Indexing (Read Only Non-Volatile)
C60, D30, D60,
F35, F60, L30,
L60, L90
3020
Number of Fault Reports
0 to 65535
---
1
F001
0
Fault Report Actual Values (Read Only Non-Volatile) (15 Modules)
C60, D30, D60,
F35, F60, L30,
L60, L90
3030
Fault Report 1 Time
0 to 4294967295
---
1
F050
0
"
3032
Fault Report 2 Time
0 to 4294967295
---
1
F050
0
"
3034
Fault Report 3 Time
0 to 4294967295
---
1
F050
0
"
3036
Fault Report 4 Time
0 to 4294967295
---
1
F050
0
"
3038
Fault Report 5 Time
0 to 4294967295
---
1
F050
0
"
303A
Fault Report 6 Time
0 to 4294967295
---
1
F050
0
"
303C
Fault Report 7 Time
0 to 4294967295
---
1
F050
0
"
303E
Fault Report 8 Time
0 to 4294967295
---
1
F050
0
"
3040
Fault Report 9 Time
0 to 4294967295
---
1
F050
0
"
3042
Fault Report 10 Time
0 to 4294967295
---
1
F050
0
"
3044
Fault Report 11 Time
0 to 4294967295
---
1
F050
0
"
3046
Fault Report 12 Time
0 to 4294967295
---
1
F050
0
"
3048
Fault Report 13 Time
0 to 4294967295
---
1
F050
0
"
304A
Fault Report 14 Time
0 to 4294967295
---
1
F050
0
"
304C
Fault Report 15 Time
0 to 4294967295
---
1
F050
0
User Programmable Fault Report Commands (Read/Write Command)
B30, B90, C70,
G30, G60, M60,
N60, T35, T60
3060
User Fault Report Clear
0 to 1
---
1
F126
0 (No)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...