2-44
UR SERIES – COMMUNICATIONS GUIDE
MEMORY MAP
CHAPTER 2: MODBUS COMMUNICATION
2
"
376B
PTP - IRIG-B Delta
-500000000 to
500000000
ns
1
F004
0
Real Time Clock Synchronizing FlexAnalogs (Read Only)
All
376D
PTP - IRIG-B Delta FlexAnalog
-262143 to 262143 ---
1
F004
0
Capacitor Control Actual Values (Read Only) (4 Modules)
C70
3780
Capacitor Control 1 Discharge Time
0 to 3600
s
1
F001
0
"
3781
Capacitor Control 2 Discharge Time
0 to 3600
s
1
F001
0
"
3782
Capacitor Control 3 Discharge Time
0 to 3600
s
1
F001
0
"
3783
Capacitor Control 4 Discharge Time
0 to 3600
s
1
F001
0
Frequency Out-of-Band Accumulation Actual Values (Read Only)
G30, G60
37A0
Frequency OOB Accumulator Band 1
Accumulation (OvUnFrecAccActualBand_1)
0.0 to 999.9
%
0.1
F001
0
"
37A1
Frequency OOB Accumulator Band 2
Accumulation (OvUnFrecAccActualBand_2)
0.0 to 999.9
%
0.1
F001
0
"
37A2
Frequency OOB Accumulator Band 3
Accumulation (OvUnFrecAccActualBand_3)
0.0 to 999.9
%
0.1
F001
0
"
37A3
Frequency OOB Accumulator Band 4
Accumulation (OvUnFrecAccActualBand_4)
0.0 to 999.9
%
0.1
F001
0
"
37A4
Frequency OOB Accumulator Band 5
Accumulation (OvUnFrecAccActualBand_5)
0.0 to 999.9
%
0.1
F001
0
"
37A5
Frequency OOB Accumulator Band 6
Accumulation (OvUnFrecAccActualBand_6)
0.0 to 999.9
%
0.1
F001
0
"
37A6
Frequency OOB Accumulator Band 7
Accumulation (OvUnFrecAccActualBand_7)
0.0 to 999.9
%
0.1
F001
0
Frequency Out-of-Band Accumulation Commands (Read/Write)
G30, G60
37A7
Reset Frequency Out-Of-Band
Accumulators
0 to 1
---
1
F126
0 (No)
"
37A8
Preset Frequency Out-Of-Band
Accumulators
0 to 1
---
1
F126
0 (No)
Phase Comparison Trip Scheme Actuals (Read Only)
L60
37B0
CT Bank1 Compensated I1 Current
0 to 999999.999
A
0.001 F060
0
"
37B2
CT Bank1 Compensated I2 Current
0 to 999999.999
A
0.001 F060
0
"
37B4
CT Bank2 Compensated I1 Current
0 to 999999.999
A
0.001 F060
0
"
37B6
CT Bank2 Compensated I2 Current
0 to 999999.999
A
0.001 F060
0
Field Units (Read/Write Setting) (8 Modules)
All except B90,
L60
3800
Field Unit 1 ID
0 to 1
---
1
F205
"U1"
"
3806
Field Unit 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
3807
Field Unit 1 Type
0 to 3
---
1
F243
0 (CC-05)
"
3808
Field Unit 1 Serial Number
1 to1
---
1
F205
"000000000
000"
"
380E
Field Unit 1 Port
1 to 4
---
1
F001
1
"
380F
...Repeated for Field Unit 2
"
381E
...Repeated for Field Unit 3
"
382D
...Repeated for Field Unit 4
"
383C
...Repeated for Field Unit 5
"
384B
...Repeated for Field Unit 6
"
385A
...Repeated for Field Unit 7
"
3869
...Repeated for Field Unit 8
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...