CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-55
2
"
4365
Total Received Port B
0 to 4294967295
---
1
F003
0
"
4367
Total Mismatches Port A
0 to 4294967295
---
1
F003
0
"
4369
Total Mismatches Port B
0 to 4294967295
---
1
F003
0
"
436B
Total Errors
0 to 4294967295
---
1
F003
0
IPv4 Route Table (Read/Write Setting) (6 Modules)
All
4370
IPv4 Network Route 1 Destination
0 to 4294967295
---
1
F003
2130706433
"
4372
IPv4 Network Route 1 Netmask
0 to 4294967295
---
1
F003
4278190080
"
4374
IPv4 Network Route 1 Gateway
0 to 4294967295
---
1
F003
2130706433
"
4376
...Repeated for Route 2
"
437C
...Repeated for Route 3
"
4382
...Repeated for Route 4
"
4388
...Repeated for Route 5
"
438E
...Repeated for Route 6
Installation (Read/Write Setting)
All
43E0
Relay Programmed State
0 to 1
---
1
F133
0 (Not
Programme
d)
"
43E1
Relay Name
---
---
---
F202
“Relay-1”
User Programmable Self Tests (Read/Write Setting)
All
4441
User Programmable Detect Ring Break
Function
0 to 1
---
1
F102
1 (Enabled)
"
4442
User Programmable Direct Device Off
Function
0 to 1
---
1
F102
1 (Enabled)
"
4443
User Programmable RxGOOSE Off Function 0 to 1
---
1
F102
1 (Enabled)
"
4444
User Programmable First Ethernet Fail
Function
0 to 1
---
1
F102
0 (Disabled)
"
4445
User Programmable Secondary Ethernet
Fail Function
0 to 1
---
1
F102
0 (Disabled)
"
4446
User Programmable Battery Fail Function
0 to 1
---
1
F102
1 (Enabled)
"
4447
User Programmable SNTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
"
4448
User Programmable IRIG-B Fail Function
0 to 1
---
1
F102
1 (Enabled)
"
444A
Process Bus Failure Operand
0 to 4294967295
---
1
F300
0
"
444C
PTP Fail Function
0 to 1
---
1
F102
1 (Enabled)
"
444D
User Programmable Third Ethernet Fail
Function
0 to 1
---
1
F102
0 (Disabled)
"
444E
User Programmable SFP Fail Function
0 to 1
---
1
F102
0 (Disabled)
CT Settings (Read/Write Setting) (6 Modules)
All except B90,
C30
4480
Phase CT 1 Primary
1 to 65000
A
1
F001
1
"
4481
Phase CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
"
4482
Ground CT 1 Primary
1 to 65000
A
1
F001
1
"
4483
Ground CT 1 Secondary
0 to 1
---
1
F123
0 (1 A)
"
4484
...Repeated for CT Bank 2
"
4488
...Repeated for CT Bank 3
"
448C
...Repeated for CT Bank 4
"
4490
...Repeated for CT Bank 5
"
4494
...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (6 Modules)
All except B90,
C30
4500
Phase VT 1 Connection
0 to 1
---
1
F100
0 (Wye)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...