CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-67
2
C60, C70, F35,
F60, L90, M60,
T60
5E06
...Repeated for Ground Instantaneous
Overcurrent 7
"
5E17
...Repeated for Ground Instantaneous
Overcurrent 8
C70, F35, T60
5E28
...Repeated for Ground Instantaneous
Overcurrent 9
"
5E39
...Repeated for Ground Instantaneous
Overcurrent 10
"
5E4A
...Repeated for Ground Instantaneous
Overcurrent 11
"
5E5B
...Repeated for Ground Instantaneous
Overcurrent 12
CT Fail (Read/Write Setting) (6 Modules)
G30, G60, L30,
L60, L90, M60,
T35, T60
5E6C
CT Fail 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
5E6D
CT Fail 1 Block
0 to 4294967295
---
1
F300
0
"
5E6F
CT Fail 1 Current Source 1
0 to 5
---
1
F167
0 (SRC 1)
"
5E70
CT Fail 1 Current Pickup 1
0 to 2
pu
0.1
F001
2
"
5E71
CT Fail 1 Current Source 2
0 to 5
---
1
F167
1 (SRC 2)
"
5E72
CT Fail 1 Current Pickup 2
0 to 2
pu
0.1
F001
2
"
5E73
CT Fail 1 Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
"
5E74
CT Fail 1 Voltage Pickup
0 to 2
pu
0.01
F001
20
"
5E75
CT Fail 1 Pickup Delay
0 to 65.535
s
0.001 F001
1000
"
5E76
CT Fail 1 Target
0 to 2
---
1
F109
0 (Self-reset)
"
5E77
CT Fail 1 Events
0 to 1
---
1
F102
0 (Disabled)
"
5E78
...Repeated for CT Fail 2
"
5E84
...Repeated for CT Fail 3
"
5E90
...Repeated for CT Fail 4
"
5E9C
...Repeated for CT Fail 5
"
5EA8
...Repeated for CT Fail 6
Incipient Cable Fault Detector Actual Values (Read Only) (2 or 6 Modules)
F35, F60
5EC0
Incipient Cable Fault Detector 1 Phase A
Counter
0 to 65535
---
1
F001
0
"
5EC1
Incipient Cable Fault Detector 1 Phase B
Counter
0 to 65535
---
1
F001
0
"
5EC2
Incipient Cable Fault Detector 1 Phase C
Counter
0 to 65535
---
1
F001
0
"
5EC3
...Repeated for Incipient Cable Fault
Detector 2
F35
5EC6
...Repeated for Incipient Cable Fault
Detector 3
"
5EC9
...Repeated for Incipient Cable Fault
Detector 4
"
5ECC
...Repeated for Incipient Cable Fault
Detector 5
"
5ECF
...Repeated for Incipient Cable Fault
Detector 6
Incipient Cable Fault Detector Command (Read/Write Setting)
F35, F60
5ED8
Incipient Cable Fault Detector Clear
Counters
0 to 1
---
1
F126
0 (No)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...