CHAPTER 2: MODBUS COMMUNICATION
MEMORY MAP
UR SERIES – COMMUNICATIONS GUIDE
2-69
2
Setting Groups (Read Only)
All except C30
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
All except C30
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
"
5F94
Setting Group 2 Name
---
---
---
F203
(none)
"
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
"
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
"
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
"
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Current Differential 87L (Read/Write Grouped Setting)
L30, L90
6000
87L Current Differential Function
0 to 1
---
1
F102
0 (Disabled)
"
6001
87L Current Differential Block
0 to 4294967295
---
1
F300
0
"
6003
87L Current Differential Signal Source 1
0 to 5
---
1
F167
0 (SRC 1)
"
6004
87L Minimum Phase Current Sensitivity
0.1 to 4
pu
0.01
F001
20
"
6005
87L Current Differential Tap Setting
0.2 to 5
---
0.01
F001
100
"
6006
87L Current Differential Phase Percent
Restraint 1
1 to 50
%
1
F001
30
"
6007
87L Current Differential Phase Percent
Restraint 2
1 to 70
%
1
F001
50
"
6008
87L Current Differential Phase Dual Slope
Breakpoint
0 to 20
pu
0.1
F001
10
"
6009
87L Current Differential Ground Function
0 to 1
---
1
F102
0 (Disabled)
"
600A
87L Current Differential Ground Pickup
0.05 to 1
pu
0.01
F001
10
"
600B
87L Current Differential Ground Restraint
1 to 50
%
1
F001
25
"
600C
87L Current Differential Ground Delay
0 to 5
seconds 0.01
F001
10
"
600D
87L Current Differential Key DTT
0 to 1
---
1
F102
1 (Enabled)
"
600E
87L Current Differential External Key DTT
0 to 4294967295
---
1
F300
0
"
6010
87L Current Differential Target
0 to 2
---
1
F109
0 (Self-reset)
"
6011
87L Current Differential Event
0 to 1
---
1
F102
0 (Disabled)
"
6012
87L Current Differential Tap 2 Setting
0.2 to 5
---
0.01
F001
100
L90
6013
87L Current Differential Signal Source 2
0 to 6
---
1
F211
0 (None)
"
6014
87L Current Differential Signal Source 3
0 to 6
---
1
F211
0 (None)
"
6015
87L Current Differential Signal Source 4
0 to 6
---
1
F211
0 (None)
Current Differential 87L In-Zone Transformer (Read/Write Grouped Setting)
L30, L90
601E
87L Inrush Inhibit Mode
0 to 3
---
1
F561
0 (Disabled)
"
601F
87L Inrush Inhibit Level
1 to 40
%fo
0.1
F001
200
Open Pole Detect (Read/Write Grouped Setting)
C60, N60
6040
Open Pole Detect Function
0 to 1
---
1
F102
0 (Disabled)
"
6041
Open Pole Detect Block
0 to 4294967295
---
1
F300
0
"
6043
Open Pole Detect A Aux Co
0 to 4294967295
---
1
F300
0
"
6045
Open Pole Detect B Aux Co
0 to 4294967295
---
1
F300
0
"
6047
Open Pole Detect C Aux Co
0 to 4294967295
---
1
F300
0
"
6049
Open Pole Detect Current Source
0 to 5
---
1
F167
0 (SRC 1)
"
604A
Open Pole Detect Current Pickup
0.05 to 20
pu
0.01
F001
20
"
604B
Open Pole Detect Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
"
604C
Open Pole Detect Voltage Input
0 to 1
---
1
F102
0 (Disabled)
"
604D
Open Pole Detect Pickup Delay
0 to 65.535
s
0.001 F001
60
"
604E
Open Pole Detect Reset Delay
0 to 65.535
s
0.001 F001
100
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...