6171
Ambient Temperature Input Sensor
0 to 32
---
1
F450
0
"
6172
Top Oil Temperature Input Sensor
0 to 32
---
1
F460
0
"
6173
January Average Ambient Temperature
-60 to 60
°C
1
F002
-20
"
6174
February Average Ambient Temperature
-60 to 60
°C
1
F002
-30
"
6175
March Average Ambient Temperature
-60 to 60
°C
1
F002
-10
"
6176
April Average Ambient Temperature
-60 to 60
°C
1
F002
10
"
6177
May Average Ambient Temperature
-60 to 60
°C
1
F002
20
"
6178
June Average Ambient Temperature
-60 to 60
°C
1
F002
30
"
6179
July Average Ambient Temperature
-60 to 60
°C
1
F002
30
"
617A
August Average Ambient Temperature
-60 to 60
°C
1
F002
30
"
617B
September Average Ambient Temperature -60 to 60
°C
1
F002
20
"
617C
October Average Ambient Temperature
-60 to 60
°C
1
F002
10
"
617D
November Average Ambient Temperature -60 to 60
°C
1
F002
10
"
617E
December Average Ambient Temperature -60 to 60
°C
1
F002
-10
Transformer Thermal Inputs (Read/Write Command)
T60
6180
Transformer Loss of Life Clear Command
0 to 1
---
1
F126
0 (No)
Transformer Percent Differential (Read/Write Grouped Setting)
G30, T35, T60
61C0
Percent Differential Function
0 to 1
---
1
F102
0 (Disabled)
"
61C1
Percent Differential Pickup
0.050 to 1.000
pu
0.001 F001
100
"
61C2
Percent Differential Slope 1
15 to 100
%
1
F001
25
"
61C3
Percent Differential Break 1
1 to 2
pu
0.001 F001
2000
"
61C4
Percent Differential Break 2
2 to 30
pu
0.001 F001
8000
"
61C5
Percent Differential Slope 2
50 to 100
%
1
F001
100
"
61C6
Inrush Inhibit Function
0 to 2
---
1
F168
1 (Adapt.
2nd)
"
61C7
Inrush Inhibit Level
1 to 40
%f
o
0.1
F001
200
"
61C8
Overexcitation Inhibit Function
0 to 1
---
1
F169
0 (Disabled)
"
61C9
Overexcitation Inhibit Level
1 to 40
%f
o
0.1
F001
100
"
61CA
Percent Differential Block
0 to 4294967295
---
1
F300
0
"
61CC
Percent Differential Target
0 to 2
---
1
F109
0 (Self-reset)
"
61CD
Percent Differential Events
0 to 1
---
1
F102
0 (Disabled)
"
61CE
Transformer Inrush Inhibit Mode
0 to 2
---
1
F189
0 (Per phase)
Transformer Inst Differential (Read/Write Grouped Setting)
T35, T60
61DA
Inst Differential Function
0 to 1
---
1
F102
0 (Disabled)
"
61DB
Inst Differential Pickup
2 to 30
pu
0.001 F001
8000
"
61DC
Inst Differential Block
0 to 4294967295
---
1
F300
0
"
61DE
Inst Differential Target
0 to 2
---
1
F109
0 (Self-reset)
"
61DF
Inst Differential Events
0 to 1
---
1
F102
0 (Disabled)
Autoreclose (Read/Write Setting) (1, 2, or 6 Modules)
D30, F35, F60,
L30
6200
Autoreclose 1 Function
0 to 1
---
1
F102
0 (Disabled)
"
6201
Autoreclose 1 Initiate
0 to 4294967295
---
1
F300
0
"
6203
Autoreclose 1 Block
0 to 4294967295
---
1
F300
0
"
6205
Autoreclose 1 Max Number of Shots
1 to 4
---
1
F001
1
"
6206
Autoreclose 1 Manual Close
0 to 4294967295
---
1
F300
0
"
6208
Autoreclose 1 Manual Reset from LO
0 to 4294967295
---
1
F300
0
"
620A
Autoreclose 1 Reset Lockout if Breaker
Closed
0 to 1
---
1
F108
0 (Off)
Products
Address Register name
Range
Units
Step
Format
Default
Summary of Contents for UR series
Page 5: ...TABLE OF CONTENTS UR SERIES COMMUNICATIONS GUIDE v INDEX...
Page 6: ...vi UR SERIES COMMUNICATIONS GUIDE TABLE OF CONTENTS...
Page 20: ...1 14 UR SERIES COMMUNICATIONS GUIDE FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1...
Page 216: ...2 196 UR SERIES COMMUNICATIONS GUIDE MEMORY MAP CHAPTER 2 MODBUS COMMUNICATION 2...
Page 428: ...A 2 UR SERIES COMMUNICATIONS GUIDE REVISION HISTORY APPENDIX A MISCELLANEOUS A...