5-154
T60 Transformer Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
c) GROUND DISTANCE
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
GROUND DISTANCE Z1(Z3)
GROUND DISTANCE Z1
GND DIST Z1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
GND DIST Z1 DIR:
Forward
Range: Forward, Reverse, Non-directional
MESSAGE
GND DIST Z1
SHAPE: Mho
Range: Mho, Quad
MESSAGE
GND DIST Z1
Z0/Z1 MAG: 2.70
Range: 0.00 to 10.00 in steps of 0.01
MESSAGE
GND DIST Z1
Z0/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
ZOM/Z1 MAG: 0.00
Range: 0.00 to 7.00 in steps of 0.01
MESSAGE
GND DIST Z1
ZOM/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1
RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 REV
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 POL
CURRENT: Zero-seq
Range: Zero-seq, Neg-seq
MESSAGE
GND DIST Z1 NON-
HOMOGEN ANG: 0.0°
Range: –40.0 to 40.0° in steps of 0.1
MESSAGE
GND DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
RGT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
LFT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...