B-54
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
FlexCurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
0 to 1
---
1
F102
0 (Disabled)
A701
Non-Volatile Latch 1 Type
0 to 1
---
1
F519
0 (Reset Dominant)
A702
Non-Volatile Latch 1 Set
0 to 65535
---
1
F300
0
A703
Non-Volatile Latch 1 Reset
0 to 65535
---
1
F300
0
A704
Non-Volatile Latch 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A705
Non-Volatile Latch 1 Events
0 to 1
---
1
F102
0 (Disabled)
A706
Reserved (4 items)
---
---
---
F001
0
A70A
...Repeated for Non-Volatile Latch 2
A714
...Repeated for Non-Volatile Latch 3
A71E
...Repeated for Non-Volatile Latch 4
A728
...Repeated for Non-Volatile Latch 5
A732
...Repeated for Non-Volatile Latch 6
A73C
...Repeated for Non-Volatile Latch 7
A746
...Repeated for Non-Volatile Latch 8
A750
...Repeated for Non-Volatile Latch 9
A75A
...Repeated for Non-Volatile Latch 10
A764
...Repeated for Non-Volatile Latch 11
A76E
...Repeated for Non-Volatile Latch 12
A778
...Repeated for Non-Volatile Latch 13
A782
...Repeated for Non-Volatile Latch 14
A78C
...Repeated for Non-Volatile Latch 15
A796
...Repeated for Non-Volatile Latch 16
Digital Counter (Read/Write Setting) (8 modules)
A800
Digital Counter 1 Function
0 to 1
---
1
F102
0 (Disabled)
A801
Digital Counter 1 Name
---
---
---
F205
“Counter 1"
A807
Digital Counter 1 Units
---
---
---
F206
(none)
A80A
Digital Counter 1 Block
0 to 65535
---
1
F300
0
A80B
Digital Counter 1 Up
0 to 65535
---
1
F300
0
A80C
Digital Counter 1 Down
0 to 65535
---
1
F300
0
A80D
Digital Counter 1 Preset
–2147483647 to
2147483647
---
1
F004
0
A80F
Digital Counter 1 Compare
–2147483647 to
2147483647
---
1
F004
0
A811
Digital Counter 1 Reset
0 to 65535
---
1
F300
0
A812
Digital Counter 1 Freeze/Reset
0 to 65535
---
1
F300
0
A813
Digital Counter 1 Freeze/Count
0 to 65535
---
1
F300
0
A814
Digital Counter 1 Set To Preset
0 to 65535
---
1
F300
0
A815
Reserved (11 items)
---
---
---
F001
0
A820
...Repeated for Digital Counter 2
A840
...Repeated for Digital Counter 3
A860
...Repeated for Digital Counter 4
A880
...Repeated for Digital Counter 5
A8A0
...Repeated for Digital Counter 6
A8C0
...Repeated for Digital Counter 7
A8E0
...Repeated for Digital Counter 8
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960
Restricted Ground Fault 1 Function
0 to 1
---
1
F102
0 (Disabled)
A961
Restricted Ground Fault 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A962
Restricted Ground Fault 1 Pickup
0.005 to 30
pu
0.001
F001
80
A963
Restricted Ground Fault 1 Slope
0 to 100
%
1
F001
40
A964
Restricted Ground Fault 1 Delay
0 to 600
s
0.01
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 46 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...