4-3
4 HUMAN INTERFACES
4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE
4
Before backing up settings and upgrading, set the
Settings > Product Setup > Security > Dual Permission Security
Access > Remote Setting Authorized
and
Local Setting Authorized
settings to "ON." Otherwise, the upgrade is blocked
and results in an "Unable to put relay in flash mode" message.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default
values, minimum/maximum values, data type, and item size) may change slightly from version to version of firm-
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
The
EEPROM DATA ERROR
message displayed after upgrading/downgrading the firmware is a resettable, self-test
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
4.1.4 ENERVISTA UR SETUP MAIN WINDOW
The EnerVista UR Setup software main window supports the following primary display components:
1.
Title bar which shows the pathname of the active data view.
2.
Main window menu bar.
3.
Main window tool bar.
4.
Site list control bar window.
5.
Settings list control bar window.
6.
Device data view windows, with common tool bar.
7.
Settings file data view windows, with common tool bar.
8.
Workspace area with data view tabs.
9.
Status bar.
10. Quick action hot links.
NOTE
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...