GE Multilin
T60 Transformer Protection System
4-11
4 HUMAN INTERFACES
4.2 EXTENDED ENERVISTA UR SETUP FEATURES
4
The following window is displayed.
Figure 4–10: TYPICAL SETTINGS FILE PROPERTIES WINDOW
3.
Enter the serial number of the T60 device to lock to the settings file in the
Serial # Lock
field.
The settings file and corresponding secure FlexLogic™ equations are now locked to the T60 device specified by the serial
number.
4.2.3 SETTINGS FILE TRACEABILITY
A traceability feature for settings files allows the user to quickly determine if the settings in a T60 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a T60 device, the date, time,
and serial number of the T60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the T60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the T60
device or obtained from the T60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
Figure 4–11: SETTINGS FILE TRACEABILITY MECHANISM
With respect to the above diagram, the traceability feature is used as follows.
2
The serial number and last setting change date
are stored in the UR-series device.
The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.
842864A1.CDR
Compare transfer dates in the settings file and the
UR-series device to determine if security
has been compromised.
1
SETTINGS FILE TRANSFERRED
TO UR-SERIES DEVICE
SERIAL NUMBER AND TRANSFER DATE
SENT BACK TO ENERVISTA AND
ADDED TO SETTINGS FILE.
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...